User manual
IEC61131 User and Reference Manual 
April 22, 2008     
236 
Inputs 
Type 
Description 
dialType 
Integer 
The types of dialing used, tone or pulse. 
0 = tone dialing 
1 = pulse dialing 
initModemString 
Message 
The initialization string to be sent to the modem. The 
string must not be more than 32 characters long. The 
function block automatically adds the "AT" and "DT" or 
"DP" commands. These commands must not be 
included in the string.  
For example the initialization string &F0 S0=1 is 
acceptable but he initialization string AT&F0 S0=1 is 
not.  
phoneNumber 
Message 
The phone number of the remote controller. The 
function block automatically adds the "AT" and "DT" or 
"DP" commands. These commands must not be 
included in the string. 
For example the phone number string 555-1212 is 
acceptable but he initialization string AT&555-1212 is 
not. 
Outputs 
Type 
Description 
done 
Boolean 
TRUE when the enable input is TRUE and the modem 
connection to the remote modem is complete. 
FALSE in all other cases. 
error 
Boolean 
TRUE when the enable input is TRUE and an error has 
occurred in the dial up. See the status output for a list of 
possible error codes. 
FALSE in all other cases. 
status 
Integer 
Status of the dialup attempt. See the modem status 
codes table below for status code information. 
Modem Status Codes 
Error Code 
Description 
0 
No Error 
1 
Bad configuration error occurs when an incorrect initialization string is sent 
to the modem. This usually means the modem does not understand a 
specific command in the initialization string. 
2 
The controller serial port is not set to RS232 Modem. 
3 
Initialization error occurs when the modem does not respond to the 
initialization string and may be turned off. 
4 
No dial tone error indicates modem is not connected to a telephone line or 
the S6 setting in the modem is too short.  
5 
Busy line indicates another device is using the phone line. 
6 
Call aborted by the program. This will occur if the enable DIAL input goes 
OFF before a modem connection occurs. 
7 
Failed to connect error occurs when there are no other errors but the 
modem failed to make a connection with the remote modem. 
8 
Carrier lost error occurs when carrier is lost for a time exceeding the S10 
setting in the modem. Phone lines with call waiting are very susceptible to 
this condition.  