IEC61131 User and Reference Manual 
April 22, 2008     
243 
dlogread 
Data Logger Extract Function Block 
Description 
The dlogread function block reads a single record in the data log identified by LogID. 
Each record in the data log is assigned a sequence number to identify the record. The 
dlogread function block and the SCADALog application use this sequence number to 
identify records in the data log. The number of data fields in a record and the data types of 
the fields are defined using the dlogcnfg function block. 
The dlogread function block pulls data from the log as Real type variables. The data 1 to 
data 8 outputs may only be connected to real variables. If a field data type is ISaGRAF 
boolean, ISaGRAF integer, or ISaGRAF timer, the output of dlogread must be converted to 
this type before connecting to the output variable. See the example below. 
enable 
readRecord 
logID 
error 
status 
dlogread 
seqNum 
data1 
data2 
data3 
data4 
data5 
data6 
seqNo 
data7 
data8 
hundredthSeconds 
Arguments 
Inputs 
Type 
Description 
enable 
Boolean 
When t he enable input changes FALSE to 
TRUE, the error and status outputs are updated. 
See the Status Code table below. 
readRecord 
Boolean 
When enable is set to TRUE, readRecord 
changes from FALSE to TRUE, data for the 
requested sequence number is read. The error and 
status outputs are also updated. See the Status 
Code table below. 
logID 
Integer 
Identifies the internal log (1 to 16). 
seqNo 
Integer 
The sequence number of the record to be read. 
Note that the seqNo is signed 32-bit integer, it will 
start from 0, increase to 2147483647 (maximum 
sign 32-bit integer), then roll over to –2415919103 
(minimum sign 32-bit integer), and then increase 
back to 0. This cycle is continuously repeated. 