User manual
IEC61131 User and Reference Manual 
April 22, 2008     
26 
PC to Controller Link 
A communication link is used to connect the ISaGRAF debugger and the target SCADAPack 
controller. The ISaGRAF debugger controls the downloading of applications to the target 
controller, monitoring the applications running in the target controller and the starting and 
stopping of applications in the target controller.  
Configuring PC-PLC Link Parameters 
The ISaGRAF PC-PLC Link parameters define how the communication link between the PC 
and the target controller functions. To open the PC_PLC link parameters dialog: 
  Select Link setup from the Debug menu. 
When selected the PC-PLC Link Parameters dialog is displayed. 
The Target Slave Number: entry is ignored when the TeleBUS Driver is selected. The 
TeleBUS Driver sets the target slave number. Ignore the value in this field. 
From the Communication port: dropdown list-box select TeleBUS Driver. 
Note:  If the TeleBUS Driver is not selectable from the Communication port: drop down 
menu then the Control Microsystems Extensions have not been installed. Refer to 
the installation CD jacket for installation information.  
The Time out (seconds): edit-box sets the length of time, in seconds, to wait for a response 
to a command from the target controller. It is an integer in the range 1 to 255 seconds. The 
default value is 3. 
Note:  This value must be set for a value larger than the Timeout value in the 
communication Protocols Configuration. See the Configuring PC Communication 
Settings section. 
The Retries: edit-box sets the number of communication attempts before a message is 
aborted. It is an integer in the range 1 to 20. The default value is 3. 
Note:  This value must be set for a value larger than the Attempts value in the 
communication Protocols Configuration. See the Configuring PC Communication 
Settings section. 
  Select the Setup button. When selected the PC Communication Settings dialog is 
displayed. 