TeleBUS Protocols Overview 
The TeleBUS communication protocols provide a standard communication interface to 
SCADAPack and TeleSAFE controllers. The TeleBUS protocols are compatible with the 
widely used Modbus RTU and ASCII protocols. Additional TeleBUS commands provide 
remote programming and diagnostics capability. 
The TeleBUS protocols operate on a wide variety of serial data links. These include RS-232 
serial ports, RS-485 serial ports, radios, leased line modems, and dial up modems. The 
protocols are generally independent of the communication parameters of the link, with a few 
exceptions.  
TeleBUS protocol commands may be directed to a specific device, identified by its station 
number, or broadcast to all devices. Using extended addressing up to 65534 devices may 
connect to one communication network. 
The TeleBUS protocols provide full access to the I/O database in the controller. The I/O 
database contains user-assigned registers and general purpose registers. Assigned 
registers map directly to the I/O hardware or system parameter in the controller. General 
purpose registers can be used by ladder logic and C application programs to store 
processed information, and to receive information from a remote device.  
Application programs can initiate communication with remote devices. A multiple port 
controller can be a data concentrator for remote devices, by polling remote devices on one 
port and responding as a slave on another port. 
The protocol type, communication parameters and station address are configured separately 
for each serial port on a controller. One controller can appear as different stations on 
different communication networks. The port configuration can be set from an application 
program, from the TelePACE programming software, or from another Modbus compatible 
device. 
Compatibility 
There are two TeleBUS protocols. The TeleBUS RTU protocol is compatible with the 
Modbus RTU protocol. The TeleBUS ASCII protocol is compatible with the Modbus ASCII 
protocol. 
Compatibility refers to communication only. The protocol defines communication aspects 
such as commands, syntax, message framing, error handling and addressing. The 
controllers do not mimic the internal functioning of any programmable controller. Device 
specific functions – those that relate to the hardware or programming of a specific 
programmable controller – are not implemented. 
Serial Port Configuration 
Communication Parameters 
The TeleBUS protocols are, in general, independent of the serial communication 
parameters. The baud rate, word length and parity may be chosen to suit the host computer 
and the characteristics of the data link. 
The port configuration can be set in four ways: 
  using the TelePACE program; 
  using the set_port function from a C application program; 