The Dial Attempts parameter specifies how many dialing attempts will be made. Valid 
values are 1 to 10. The default value is 1.  
The Connect Time parameter specifies the amount of time in seconds the modem will wait 
for a connection. Valid values are 6 to 300. The default value is 60. 
The Pause Time parameter specifies the time in seconds between dialing attempts. Valid 
values are 6 to 600. The default value is 30. 
Check the Inactivity Timeout check box to automatically terminate the dialup connection 
after a period of inactivity. The Inactivity Time edit box is enabled only if this option is 
checked. The default state is checked. 
Enter the inactivity period, in minutes, in the Inactivity Timeout box. The dialup connection 
will be terminated automatically after the specified number of minutes of inactivity has 
lapsed. This option is only active if the Inactivity Timeout box is checked. Valid values are 
from 1 to 30 minutes. The default value is 1. 
  Click Restore Defaults to restore default values to all fields on this page, except for the 
Phone Number field. The content of this field will remain unchanged. 
Advanced Parameters 
DNP Configuration Advanced parameters set the DNP master station address and message 
size control. When the Advanced tab heading is clicked the Advanced dialog is opened as 
shown below. 
Figure 8: DNP Configuration (Advanced) Dialog Box 