An application program, written in TelePACE Ladder Logic or TelePACE C++ Tools and 
ISaGRAF IEC61131 or ISaGRAF IEC61131 C++ Tools programming, enables and 
configures store and forward messaging. A HMI host may enable and configure store and 
forward messaging through the controller I/O database. 
TelePACE Ladder Logic 
When a SCADAPack 330, SCADAPack 350, SCADAPack 32 or SCADAPack 32P 
controllers are used the store and forward translation table is configured using an Element 
Configuration dialog. From the Controller menu select the Store and Forward command 
to access the element configuration. Refer to the TelePACE Ladder Logic Program 
Reference Manual for complete information on using the Store and Forward element 
configuration. 
The translation table must be initialized before store and forward messaging is enabled. 
Forwarding of messages is disabled when TelePACE programming software or a SERVICE 
boot initializes the controller. This prevents inadvertent forwarding of messages when new 
controllers are installed on networks. 
TelePACE C++ Tools 
The SCADAPack 32 C++ language application program interface provides the following 
functions. Refer to the SCADAPack 32 C++ Tools Reference and User Manual for details. 
  The getSFTranslation function returns an entry from the store and forward translation 
table. The entry consists of two port and station address pairs. 
  The setSFTranslation function writes an entry into the store and forward translation 
table. The entry consists of two port and station address pairs. The function checks for 
invalid translations; if the translation is not valid it is not stored. The function returns a 
status code indicating success or an error if the translation is not valid. A translation is 
cleared from the table by writing a translation with both stations set to 
DISABLED_STATION (65535). 
  The clearSFTranslationTable function clears all entries in the translation table. A 
cleared entry has the port set to 0 (com1) and the station set to DISABLED_STATION 
(65535). 
  The checkSFTranslationTable function checks the translation table for invalid entries. It 
returns a status structure indicating if the table is valid and the location and type of the 
first error if it is not valid. 
ISaGRAF IEC61131 
1.  To enable the use of store and forward messaging on one or more serial ports the 
Custom Function setprot or setprot2 must be added to the project. The SandFEnabled 
input must be set to TRUE. 
2.  Configure the translation table by using the setsfip2 function to write the necessary 
translation table entries. 
The translation table must be initialized before store and forward messaging is enabled. 
Forwarding of messages is disabled when ISaGRAF IEC61131 programming software or a 
SERVICE boot initializes the controller. This prevents inadvertent forwarding of messages 
when new controllers are installed on networks. 
ISaGRAF IEC61131 C++ Tools 
The SCADAPack 32 C++ language application program interface provides the following 
functions. Refer to the SCADAPack 32 C++ Tools Reference and User Manual for details. 