User manual
IEC61131 User and Reference Manual 
April 22, 2008     
514 
The Event Reporting Method selection specifies how binary input events are reported. A Change 
Of State event is an event object, without time, that is generated when the point changes state. Only 
one event is retained in the buffer for each point. If a subsequent event occurs for a point, the 
previous event object will be overwritten. The main purpose of this mode is to allow a master station 
to efficiently poll for changed data. A Log All Events is event object with absolute time will be 
generated when the point changes state. All events will be retained. The main purpose of this mode is 
to allow a master station to obtain a complete historical data log. The selections are: 
  Change of State 
  Log All Events 
The Event Buffer Size parameter specifies the maximum number of binary input change events 
buffered by the RTU. The buffer holds all binary input change events, regardless of the class to 
which they are assigned. If the buffer is completely full the RTU will lose the oldest events and 
retain the newest; the ‘Event Buffer Overflowed’ IIN flag will also be set to indicate that the buffer 
has overflowed. The Event Buffer size should be at least equivalent to the number of binary inputs 
defined as Change of State type. This will allow all binary inputs to change simultaneously without 
losing any events. The value of this parameter depends on how often binary input change events 
occur and the rate at which the events are reported to the master station. The valid values for this 
parameter are 0 - 65535. Default value is 16. 
The Allow Duplicate Modbus Addresses checkbox determines if the Modbus I/O database 
addresses assigned to the DNP data points must be unique. Check this box if you want to allow more 
than one point to use the same Modbus address. 










