User manual
IEC61131 User and Reference Manual 
April 22, 2008     
555 
Event Buffers shows the number of events in each type of event buffer and the allocated buffer size. 
The buffers shown are for binary inputs, 16-bit analog inputs, 32-bit analog inputs, Floating point 
analog inputs, 16-bit counter inputs, and 32-bit counter inputs, and Class 1, 2, and 3 events. 
The Event Buffers window displays the number of events in each type of event buffer and the 
allocated buffer size for the selected remote station. The event buffers displayed are: 
  Binary In (binary inputs) 
  AIN-16 (16-bit analog inputs) 
  AIN-32 (32-bit analog inputs) 
  AIN-Float (floating point analog inputs) 
  Counter-16 (16-bit counter inputs) 
  Counter-32 (32-bit counter inputs) 
  Class 1 (class 1 events) 
  Class 2 (class 2 events) 
  Class 3 (class 3 events) 
Note:  Due to a limitation of the DNP3 protocol, an Unsolicited message from an outstation 
is not capable of including information stating which data class generated the 
message. As a result, all Unsolicited events when received by the master will be 
counted as Class 1 events. Events which are polled by the master, however, do 
contain class information and will be counted in the Event Buffer for the appropriate 
class. 