User manual
IEC61131 User and Reference Manual 
April 22, 2008     
557 
Device Name:  SCADAPack controllers 
Highest DNP Level Supported: 
For Requests  2 
For Responses 2 
Device Function:  
  Master   Slave 
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels 
Supported (the complete list is described in the attached table): 
  Function code 14 (warm restart) 
  Function code 20 (Enable Unsolicited Messages) for class 1, 2, 3 objects only. 
  Function code 21 (Disable Unsolicited Messages) for class 1, 2, 3 objects only. 
  Object 41, variation 1 (32-bit analog output block) 
Maximum Data Link Frame Size (octets): 
Transmitted  292 
Received   (must be 292) 
Maximum Application Fragment Size (octets): 
Transmitted    2048 
Received    2048 
Maximum Data Link Re-tries: 
  None 
  Fixed at 
  Configurable, range 0 to 255 
Maximum Application Layer Re-tries: 
  None 
  Configurable, range 0 to 255 
Requires Data Link Layer Confirmation: 
 Never 