User manual
IEC61131 User and Reference Manual 
April 22, 2008     
571 
DNP V3.00 
DEVICE PROFILE DOCUMENT 
IMPLEMENTATION OBJECT 
This table describes the objects, function codes and qualifiers used in the device: 
OBJECT 
REQUEST 
(slave must parse) 
RESPONSE 
(master must parse) 
Obj 
Var 
Description 
Func 
Codes 
(dec) 
Qual 
Codes 
(hex) 
Func 
Codes 
Qual 
Codes 
(hex) 
21 
0 
Frozen Counter - All Variations 
1 
06 
21 
1 
32-Bit Frozen Counter 
129, 130 
00, 01 
21 
2 
16-Bit Frozen Counter 
129, 130 
00, 01 
21 
3 
32-Bit Frozen Delta Counter 
21 
4 
16-Bit Frozen Delta Counter 
21 
5 
32-Bit Frozen Counter with Time of Freeze 
21 
6 
16-Bit Frozen Counter with Time of Freeze 
21 
7 
32-Bit Frozen Delta Counter with Time of 
Freeze 
21 
8 
16-Bit Frozen Delta Counter with Time of 
Freeze 
21 
9 
32-Bit Frozen Counter without Flag 
129, 130 
00, 01 
21 
10 
16-Bit Frozen Counter without Flag 
129, 130 
00, 01 
21 
11 
32-Bit Frozen Delta Counter without Flag 
21 
12 
16-Bit Frozen Delta Counter without Flag 
22 
0 
Counter Change Event - All Variations 
1 
06,07,08 
22 
1 
32-Bit Counter Change Event without Time 
129, 130 
17, 28 
22 
2 
16-Bit Counter Change Event without Time 
129, 130 
17, 28 
22 
3 
32-Bit Delta Counter Change Event without 
Time 
22 
4 
16-Bit Delta Counter Change Event without 
Time 
22 
5 
32-Bit Counter Change Event with Time 
22 
6 
16-Bit Counter Change Event with Time 
22 
7 
32-Bit Delta Counter Change Event with Time 
22 
8 
16-Bit Delta Counter Change Event with Time 
23 
0 
Frozen Counter Event - All Variations 
23 
1 
32-Bit Frozen Counter Event without Time 