Duplex 
The TeleBUS DF1 protocols communicate in one direction at a time. However the duplex 
setting is determined by the type of serial data link used. The table below shows the possible 
settings for the controller. Note that not all port types are available on all controllers. 
Port Type 
Possible 
Settings 
Recommended Setting 
RS-232 or 
RS-232 
Dial-up 
modem 
half duplex 
full duplex 
Use full duplex wherever 
possible. 
Use half duplex for most 
external modems. 
RS-485 
half duplex 
full duplex 
Slave stations always use 
half duplex. 
Master stations can use full 
duplex only on 4 wire 
systems. 
Protocol Parameters 
The TeleBUS DF1 protocols operate independently on each serial port. Each port may set 
the protocol type, station number, protocol task priority and store-and-forward messaging 
options. 
The protocol configuration can be set in four ways: 
  using the TelePACE or ISaGRAF programs; 
  using the set_protocol function from a C application program; 
  writing to the I/O database from a C or ladder logic application program; or 
  writing to the I/O database remotely from a Modbus or DF1 compatible device. 
To configure protocol settings through the I/O database, add the module, CNFG Protocol 
settings, to the Register Assignment. 