User's Manual
Table Of Contents
- 1 Introduction
 - 2 Quick Guide to setting up S610S
 - 3 Connecting an S610S Master Reader
- 3.1 Open the S610 reader case
 - 3.2 S610S Master Reader 12V Power and Data connections
 - 3.3 Extra settings required, made on the reader
 - 3.4 Addressing an S610S master reader
 - 3.5 S610S Connecting Master Reader Inputs
 - 3.6 Monitoring Inputs for Cable Tampers
 - 3.7 Using an external read head
 - 3.8 S610S Lock and spare output relay connections
 
 - 4 Connecting an S610S to an Exit Reader
 - 5 Connecting an S610S to a DIU
 - 6 AC2000 Devices Application tasks
 - 7 Door Modes
 - 8 Interlock
 - 9 Other AC2000 software configurations
 - 10 S610S onboard diagnostic mode
 - 11 Appendix
 
S610S Manual - Hardware Installer Manual - Version 1.8 
  7 
How to use an S610S reader 
Swipe a card over the keypad area, then enter a keypad command or PIN if required to do so. 
LED Card Response table 
Green  Card Valid  Description 
Flashing Green  Card Expiring  Consult System Admin to extend Card Expiry date 
Amber  Wrong Zone 
Wrong Time zone 
Passback failure 
Wrong PIN 
Door not in card holder’s Access Level. 
Door is in Card Holders Access level but not Time Zone. 
Card holder must comply with site access policy. 
Swipe again and enter correct PIN. 
Red – Invalid card 
Flashing Red 
Card error - retry 
Card not in system 
Card expired 
Lost or Stolen Card 
Try again; if fault persists consult your system administrator. 
Consult your system administrator or site security office. 
Consult your system administrator or site security office. 
Consult your system administrator or site security office. 
1.1  Cabling requirements 
Cable needed    Connector type 
2 pair (Belden 8723) cable, DataA, DataB, GND and 12V  4 way JST – J15 
6 pair (Belden 8723) maximum Inputs and 
Outputs 
8 way JST – J6 and  
6way socket – J12 
2 pair (Belden 8723) power/comms to Exit reader  4 way JST – J5 to J5 










