User's Manual

Table Of Contents
AC2000 Getting Started Guide
27
3.11.1 Configuration information
Using a CEM DIU230 provides the highest level of security at a door, removing power for the
lock and input monitoring away from the door reader. The DIU is a PoE+ device and does not
require specialist electrical qualifications to install.
Input configuration
When a DIU230 is used with a emerald terminal, the DIU controls the main CEM reserved
inputs and the inputs on the readers become spare. The exception to this is input three on the
emerald terminal (input B in the table below) which maintains its status as being used for
interlock mode.
.
Important
If a decision has been made not to connect a fire and break glass units to the DIU the inputs must be linked out to
ensure that the DIU functions normally. The tamper input must also be linked out when not in use to prevent
alarms being generated on AC2000.
Product CEM Product Code
DIU 230 PoE+ (board only) DIU/700/230
DIU 230 PoE+ (with enclosure) DIU/700/231
Table 18: DIU230 product codes
Input
number
Input
location
Input function Default input trigger state change
0 DIU Door position short => open
1 DIU Lock position short => open
2 DIU Request to exit switch open => momentary short => open
3 DIU Fire short => open
4 DIU Breakglass short => open
5 DIU Mains power fail Internally triggered
6 DIU Battery low Internally triggered
7 DIU DIU tamper short => open
8Master
terminal
Spare short => open
9Master
terminal
Spare short => open
AMaster
terminal
Spare short => open
BMaster
terminal
Spare / Interlock short => open
C Exit reader Spare normally open
D Exit reader Spare normally open
E Exit reader Spare normally open
F Exit reader Spare normally open
Table 19: emerald and DIU230 input configuration