Owner manual
3.1.2 Wiring the AUX
Relay for Use as
Alarm Shunt
The Alarm Shunt Relay function may be necessary
when a separate existing security system is in place.
The Alarm Shunt Relay keeps an alarm panel zone
from going into alarm when the door is opened, after
a valid code is entered. The Alarm Shunt function is
assigned to the Aux relay by default. To incorporate
this feature, follow the steps below; see Figure 3-2.
3.1.2.A Wiring the Alarm Shunt Relay
1. Turn OFF power to the prox.pad plus unit, and
then unlatch the keypad from the plastic housing.
2. Locate connector P2 (the 6-pin connector) on the
main circuit board and plug on the 6-pin harness.
(The 2-pin jumper on pins 5 and 6 of connector
P2 must be removed first.)
3. Connect the 6-conductor harness to connector P2
as shown in Figure 3-2.
4. Connect the blue wire to the “Common” side of
the door contact.
5. Connect the green wire to the “Normally Open”
side of the door contact.
6. Make a parallel connection to the green and blue
wires and run the leads to the alarm panel. NOTE:
This feature requires that you use the “Door Con-
tact”inputasshowninFigure3-1.
7. Restore power to the keypad and test.
3.1 Wiring the prox.pad plus Unit Chapter 3: Wiring
prox.pad plus Install/Program. Manual, PPP, D4b 3-3