10 - Edition 08/2014 Cod. 2200791683 01 -
18.0 STARTING UP
BEFORE CARRYING OUT ANYOPERATION ON THE MACHINE, ENSURE THAT THE ELECTRIC POWER SUPPLY HAS BEEN
DISCONNECTED
18.1 PRELIMINARY CONTROLS
Before starting the dryer, check:
- The correct connection to the compressed air piping: remember to remove eventual caps on the drier inlet and outlet.
- The correct connection to the condensate drainage system.
- That the power supply is right.
18.2 STARTING AND STOP
Start the system before the air compressor starts running and stop it after the air compressor has been stopped. The
compressed air piping will be free of condensate only by doing so. The drier must be kept running during all the time the
air compressor is running. WARNING: if the drier is switched off, before starting it again, wait at least 5 minutes in order
to allow the pressure balancing.
BEFORE CARRYING OUT ANY MAINTENANCE JOBS IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM THE
POWER MAINS AND FROM THE COMPRESSED AIR DISTRIBUTION NETWORK.
PRESSURE DISCHARGE PROCEDURE
Proceed as follows:
- Close the taps Ref. 1 Fig. 11
- Release the pressure in the dryer by pressing the condensate drain “TEST” pushbutton locate on the steam trap
Ref. 1 Fig. 11
- Switch off the machine by pressing the STOP button Ref. 3 Fig. 11
- Turn on the supply automatic differential switch Ref. 4 Fig. 11
CALIBRATIONS
BYPASS VALVE FOR HOT GAS
N.B.These valves have already been calibrated and they do not require any adjistment. A dew point different from the
rated one generally depends on causes which are not attributable to their operation.
Ref. 1) Closing cap
Ref. 2) Adiusting screw
WORKING PRESSURES AND TEMPERATURES OF R404A
SUCTION SIDE OF
REFRIGERATION COMPRESSOR
Evaporat.
Temperat.
°C (°F)
Evaporating
Pressure bar (psi)
RATED VALUES
(Temperat.
20°C – 68°F)
1 ÷ 2
(33,8 ÷ 35,6)
R404A
4,3 ÷ 4,5
(62,3 ÷ 65,2)
2
1
1
FIG. 11
4
3
2