Unit installation
27
CLEARANCES
The installation clearances to be maintained for the various unit models are as follows:
CORNER WALL
FIGURE 2
B
2000
2000
STRAIGHT WALL
FIGURE 1
WALL
A B
Notes:
1. All above dimensions are in mm.
2. PIT INSTALLATION: If unit is installed in special pit, please observe the same tolerance for walls.
Pit heights should not exceed Chiller height.
VIBRATION ISOLATION AND SCHEMATIC MOUNTING LAYOUTS
Vibration isolators are necessary for installing these chillers in order to minimize the transmission of vibrations. The
two types of vibration isolators generally utilized for mounting these units are Neoprene Pads and Spring Isolators.
Neoprene Pads are recommended for ground level normal installations jobs where vibration isolation is not critical and
job costs must be kept to a minimum. Spring Isolators are recommended for ground level installations which are
noise-sensitive areas or exposed to wind loads and all roof top installations. For extremely noise and vibration
sensitive areas, follow the recommendations of structural and acoustical consultants.