Unit installation
35
• Thermometer and pressure gauge connections should be provided on the inlet and outlet connections of each
cooler. Pressure gauges are recommended to check the water pressure before and after the cooler and to
determine if any variations occur in the cooler and system. When installing pressure taps to measure the amount of
pressure drop across the water side of the cooler, the taps should be located in the water piping a minimum of 24
inches downstream from any connection (flange etc.) but as near to the cooler as possible.
• Drain and air vent connections should be provided at all low and high points in the piping system to permit complete
drainage of the cooler and piping as well as to vent any air in the pipes. Hand shut-off valves are recommended for
use in all lines to facilitate servicing.
• The system water piping must be flushed thoroughly before connecting to the unit cooler. The cooler must not be
exposed to flushing velocities or debris released during flushing. It is recommended that a suitably sized bypass
and valve arrangement is installed to allow flushing of the piping system. The bypass can be used during
maintenance to isolate the cooler without disrupting flow to other units.
Any debris left in the water piping between the strainer and cooler could cause
serious damage to the tubes in the cooler and must be avoided. The
contractor/owner must also ensure that the quality of the water in circulation is
satisfactory, without any dissolved gases which can cause oxidation of steel
parts within the cooler.
• The following is a suggested piping arrangement at the chiller for single unit installations. For multiple chiller
installations, each unit should be piped as shown:
IN
Isolating Valve - Normally Closed
Isolating Valve - Normally Open
Flow meter
Strainer
Balancing Valve
Pipe work
Flexible connection
Connection (flanged / Victaulic)
Pressure tapping
Flow Switch
OUT
Note: For chillers with two coolers, the connecting pipes for entering and leaving water on one cooler must be joined
to the corresponding pipes on the other cooler before connecting to the main headers in the system piping.
CAUTION
!