ELECTRICAL CONNECTIONS, POWER AND CONTROL WIRING
All units are wired completely at the factory prior to delivery. The connections that must be made by the installer are to
the main power source and interlocking with water flow switch, pumps, remote monitoring system and two barrel units
water temperature sensor, if any.
In connecting power wiring to the unit, the following guidelines must be followed to ensure safe and satisfactory
operation of the units. Failure to follow these recommendations could cause harm to personnel or damage to the unit
and may nullify the warranty:
All field wiring should be carried out in accordance with the National Electrical Code (NEC) and local codes.
All wiring is to be checked for damages and all terminal connections for tightness. All wiring to the unit should use
copper conductors only, sized based on the minimum circuit ampacity (MCA) values given in the Electrical Data
Section of this manual or the unit nameplate.
The power supply should match the unit nameplate in volts, phase and Hertz. The voltage imbalance between
phases must not exceed 2%.
Main power must be supplied from a single field supplied and mounted Disconnect
switch, using dual element time delay fuse or circuit breaker.
If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
No additional controls (relays, etc.) should be mounted in the unit control panel unless
recommended by Zamil. Power and control wiring not connected to the unit should not
be run through the unit control panel. If these precautions are not observed it could
lead to a risk of electrocution or nuisance faults.
After connection of wiring, do not switch ON main power to the unit out rightly. Some
internal components get live when the main disconnect is switched ON and this must
be done by authorized personnel only.
If the unit is mounted on spring vibration isolators, electrical service to the unit must
also be flexibly connected (by means of a suitable flexible conduit), as some
movement of the unit can be expected during normal operation.