Unit installation

Nominal RL
A
LR
A
CB RL
A
LR
A
CB
FLA TOTAL
CB Total Total
(V-Ph-Hz) (each) (each) Poles MTA QTY. (each) (each) Poles MTA QTY. (each) KW QTY Watts Amps
ASQ045B
380/415-3-50 342 456 115 198 1
82.4
423 3 66 2 - - - - - - 4 3.12 4.40 12.48 2 230 200
0.87
PW
ASQ050B
380/415-3-50 342 456 123 212 1
88.8
423 3 71 2 - - - - - - 4 3.12 4.40 12.48 2 230 200
0.87
PW
ASQ055B
380/415-3-50 342 456 142 245 1
103.5
520 3 83 2 - - - - - - 4 3.12 4.40 12.48 2 230 300
1.30
PW
ASQ060B
380/415-3-50 342 456 161 281 1
119.2
612 3 95 2 - - - - - - 4 3.12 4.40 12.48 2 230 300
1.30
PW
ASQ070B
380/415-3-50 342 456 184 322 1
137.8
665 3 110 2 - - - - - - 4 3.00 5.40 12 2 230 300
1.30
PW
ASQ080B
380/415-3-50 342 456 203 286 2
82.4
423 3 66 4 - - - - - - 6 3.00 8.10 18 3 230 400
1.74
PW
ASQ090B
380/415-3-50 342 456 218 307 2
88.8
423 3 71 4 - - - - - - 6 3.00 8.10 18 3 230 400
1.74
PW
ASQ100B
380/415-3-50 342 456 251 354 2
103.5
520 3 83 4 - - - - - - 6 3.00 8.10 18 3 230 600
2.61
PW
ASQ115B
380/415-3-50 342 456 292 411 2
119.2
612 3 95 4 - - - - - - 8 3.00 10.80 24 4 230 600
2.61
PW
ASQ130B
380/415-3-50 342 456 334 472 2
137.8
665 3 110 4 - - - - - - 8 3.00 10.80 24 4 230 600
2.61
PW
ASQ140B
380/415-3-50 342 456 340 478 2
137.8
665 3 110 4 - - - - - - 10 3.00 13.50 30 5 230 600
2.61
PW
ASQ150B
380/415-3-50 342 456 364 512 2
148.3
665 3 119 4 - - - - - - 10 3.00 13.50 30 5 230 600
2.61
PW
ASQ160B
380/415-3-50 342 456 372 476 3
103.5
520 3 83 6 - - - - - - 12 3.00 16.20 36 6 230 900
3.91
PW
ASQ170B
380/415-3-50 342 456 406 524 2
118.3
520 3 95 4 1
103.5
520 3 83 2 12 3.00 16.20 36 6 230 900
3.91
PW
ASQ180B
380/415-3-50 342 456 454 587 2
132.8
612 3 106 4 1
119.2
612 3 95 2 12 3.00 16.20 36 6 230 900
3.91
PW
ASQ190B
380/415-3-50 342 456 468 600 3
132.8
612 3 106 6 - - - - - - 12 3.00 16.20 36 6 230 900
3.91
PW
ASQ200B
380/415-3-50 342 456 484 622 3
137.8
665 3 110 6 - - - - - - 12 3.00 16.20 36 6 230 900
3.91
PW
ASQ220B
380/415-3-50 342 456 523 642 2
119.2
612 3 95 4 2
103.5
520 3 83 4 16 3.00 21.60 48 8 230 1,200
5.22
PW
ASQ230B
380/415-3-50 342 456 555 674 4
119.2
612 3 95 8 - - - - - - 16 3.00 21.60 48 8 230 1,200
5.22
PW
ASQ240B
380/415-3-50 342 456 578 716 1
137.8
665 3 110 2 3
119.2
612 3 95 6 16 3.00 21.60 48 8 230 1,200
5.22
PW
ASQ250B
380/415-3-50 342 456 596 734 2
137.8
665 3 110 4 2
119.2
612 3 95 4 16 3.00 21.60 48 8 230 1,200
5.22
PW
ASQ260B
380/415-3-50 342 456 596 734 2
137.8
665 3 110 4 2
119.2
612 3 95 4 16 3.00 21.60 48 8 230 1,200
5.22
PW
ASQ270B
380/415-3-50 342 456 634 771 4
137.8
665 3 110 8 - - - - - - 16 3.00 21.60 48 8 230 1,200
5.22
PW
ASQ280B
380/415-3-50 342 456 657 806 2
148.3
665 3 119 4 2
137.8
665 3 110 4 16 3.00 21.60 48 8 230 1,200
5.22
PW
ASQ300B
380/415-3-50 342 456 671 775 4
103.5
520 3 83 8 2
88.8
423 3 71 4 18 3.00 24.30 54 9 230 1,600
6.96
PW
ASQ320B
380/415-3-50 342 456 734 852 2
118.3
520 3 95 4 4
103.5
520 3 83 8 18 3.00 24.30 54 9 230 1,800
7.83
PW
ASQ330B
380/415-3-50 342 456 749 867 3
118.3
520 3 95 6 3
103.5
520 3 83 6 18 3.00 24.30 54 9 230 1,800
7.83
PW
ASQ340B
380/415-3-50 342 456 799 918 6
119.2
612 3 95 12 - - - - - - 18 3.00 24.30 54 9 230 1,800
7.83
PW
ASQ350B
380/415-3-50 342 456 811 930 6
119.2
612 3 95 12 - - - - - - 22 3.00 29.70 66 11 230 1,800
7.83
PW
ASQ360B
380/415-3-50 342 456 855 988 3
132.8
612 3 106 6 3
119.2
612 3 95 6 22 3.00 29.70 66 11 230 1,800
7.83
PW
ASQ380B
380/415-3-50 342 456 890 1028 4
137.8
665 3 110 8 2
119.2
612 3 95 4 22 3.00 29.70 66 11 230 1,800
7.83
PW
ASQ400B
380/415-3-50 342 456 927 1065 6
137.8
665 3 110 12 - - - - - - 22 3.00 29.70 66 11 230 1,800
7.83
PW
ASQ420B
380/415-3-50 342 456 961 1110 3
148.3
665 3 119 6 3
137.8
665 3 110 6 22 3.00 29.70 66 11 230 1,800
7.83
PW
ASQ440B
380/415-3-50 342 456 993 1141 6
148.3
665 3 119 12 - - - - - - 22 3.00 29.70 66 11 230 1,800
7.83
PW
LEGENDS: NOTES:
MCA -Minimum Circuit Ampacity per NEC 430-24
1. Main power must be supplied from a single field supplied and mounted fused disconnections using dual element time delay fuse or circuit breaker.
MOCP -Maximum Over Current Protection
2. The maximum incoming wire size is 500MCM. On units having MCA greater than 500MCM wire, the factory supplied terminal block will accept two or more parallel field wires per pole phas
e
RLA -Rated Load Amps
3. The compressor crankcase heaters must be energized for 12 hours before the unit is initally started or after a prolonged power disconnection.
LRA -Locked Rotor Amps
4. All Field Wiring must be in accordance with NEC and local standards.
CB -Circuit Breaker
5. Minimum and Maximum unit supply voltage are shown in the tabulated data above.
FCA -Fan Circuit Amps
6. Neutral line is required on 380/415V-3Ph-50Hz (4 wires) power supply.
MTA -Must Trip Amps
7. The + / - 10 % voltage variation from the nominal is accepted for short time and not permanent.
MOC -Max. operating current
8. Customer to specify the exact nominal power supply available at the site so that electrical components are selected accurately, failing to do so will affect unit performance & terms of warrant
y
HP -Horse Power
9. Under compressor type 1 are the big compressor or compressor with economizer and under type 2 are the small compressor or compressor without economizer.
PH -Phase
PW -Part Windin
g
Start Com
p
ressor
ELECTRICAL DATA
QTY.QTY.
Supply Voltage
CB
MOCP QTY.
CB
COMPRESSOR TYPE1 COMPRESSOR TYPE2
COMP.
WINDING
UNIT SIZE
MIN MAX MCA
CRANKCASE HEATER
FCA Volts
CONDENSER FAN
39