Unit installation
46
Model
ASQ-B
CURVE NO. MINIMUM GPM Maximum GPM
045
1
73 122
050
1
82 125
055
1
87 149
060
1
92 163
070
1
111 189
080
1
125 219
090
2
165 242
100
2
165 273
115
3
197 322
130
3
227 353
140
4
239 382
150
4
279 397
160
5
267 435
170
5
305 456
180
5
321 494
190
6
338 516
200
6
336 544
220
3
377 615
230
3
388 638
240
3
406 657
250
3
430 680
260
4
439 722
270
4
470 757
280
4
504 768
300
5
526 833
320
5
567 887
330
5
584 895
340
5
566 943
350
5
594 972
360
5
640 992
380
6
657 1070
400
6
686 1104
420
7
773 1167
440
7
827 1184
CONVERSION FACTOR : GPM = 0.063 L/S
: ftH2O=2.989 kPA
The above water flow rate limits must not be exceeded at any time. Operation
outside this range might result in cooler failure. Special care should be taken
when multiple chillers are fed by a single pump.
When using glycol solution, flow rate and pressure drop are higher than with
water. Special care must be taken not to exceed the limits. Consult Zamil for
further information and guidance in this regard.
ATTENTION
(
CAUTION
!