Trial Operation
Procedure and Summary of Trial Operation
NOTE 1: Criteria for indoor air inlet/outlet temperature difference
After operation for a minimum of 30 minutes in “COOL” mode, if temp. difference
between the air inlet and air outlet of the indoor unit is 8°C or more – operation
is normal.
(In Max. Hz operation)
The difference in temperature between the air inlet and air outlet decreases
when the total number of indoor units connected, exceeds 100% of the system
capacity, or when the pipe length exceeds specification.
NOTE 2: Criteria of operation current value
In cooling operation, when the current is within ± 15% of the specified current
value, the system is operating normally.
(COOL Max. Hz operation)
The current value differs as described below according to the operation conditions.
Greater than the specified current
(1) Temp. in indoor/outdoor is high.
(2) Radiation of outdoor unit is bad.
Less than the specified current
(1) Temp. in indoor/outdoor is low.
(2) Gas leakage. (Insufficient refrigerant amount)
NOTE 3: Criteria of operation pressure
COOL/
High pressure 16 to 22kgf/cm
2
G
Indoor 18 to 32°C
HEAT
Low pressure 3.5 to 5.5kgf/cm
2
G
Outdoor 25 to 35°C
NOTE: Measurement taken 15 minutes after operation start (Dry bulb temp. °C)