Service manual

Troubleshooting
Diagnostic Procedure for Check Code
90
14
Check code Operation cause
1. Ps sensor error
2. Service valve closed
3. Indoor fan capacitor error
[bE] 4. Indoor/outdoor PMV blockage
Low-pressure protective operation 5. Indoor heat exchanger blockage
6. SV2 circuit
7. Incorrect wiring of communication cable between
indoor and outdoor units
Does the indoor fan operate?
Is there a blockage on the
indoor filter or heat exchanger?
Repair defective part.
Check indoor P.C. board.
If defective, replace.
Replace low-pressure sensor.
Clean or remove blockage.
No
Yes
No
Yes
Yes
Are the characteristics of
low-pressure sensor normal?
No
Yes
Insufficient refrigerant,
blockage, pipe breakage.
(Check miswiring of the outdoor unit according to miswiring check function.)
Set normal wiring.
Is the wiring correct?
No
Yes
Open valves fully.
Are the gas pipe and liquid
pipe service valves of the
outdoor unit fully open?
Are the following
items related to indoor
fan motor normal?
1. Connection
2. Capacitor
3. Motor
No
Yes
Modify SV2 bypass circuit.
Is SV2 bypass circuit normal?
No
Yes
No