Electronics Power Supply User Manual

POWERPATH NAC POWER SUPPLIES
Description
The Wheelock Series PS-6 and PS-8 are 24VDC, filtered and
regulated, supervised remote power supply/battery chargers are
used for supervision and expanded power driving capability of Fire
Alarm Notification Appliance Circuits. The PS-6 provides 6 amps of
power distributed across 4 outputs, while the PS-8 provides 8 Amps
across 4 output. In addition the PS-8 provides additional room in
the chassis for accessories like an Addressable Control Module, with
mounting studs.
The Power Supplies may be connected to any 12V or 24V (FWR or
DC) Fire Alarm Control Panel (FACP) by using a Notication Appliance
Circuit (NAC) or a Dry Contact. Primary applications include NAC
expansion (supports ADA requirements) and auxiliary power to
support system accessories. This unit provides ltered and regulated
24VDC, up to four (4) Class B, two (2) Class “A”, or two (2) Class
“B” and one (1) Class “A Notification Appliance Circuits. With the
optional plug-in PS-EXP module the unit supports (8) Class “B” or
(4) Class A Notification Appliance Circuits. Additionally, an auxiliary
power output of 2.5 Amps (disconnected upon AC power loss or an
alarm condition) or up to 0.240 A of constant power on the PS-8 and
0.075 A of constant power on the PS-6.
The Wheelock Power Supplies can accommodate 7 or 12 AH batteries
inside its lockable chassis. Using an external battery cabinet it can
charge up to 33 AH batteries (pending UL testing). Two FACP NAC
circuits or two “Dry” contact initiating circuits can be connected to the
inputs. These inputs can then be directed to control supervision and
power delivery to any combination of the four (4) outputs. Each output
is rated at 3.0 Amps (Class “B”) or (Class A”) and can be programmed
to generate a steady or Code 3 Temporal Horn sound and a strobe
output under alarm condition. Total load for the PS-6 and PS-8 NAC
circuits must not exceed the power supplies rated output.
The Power Suppliesunder non-alarm condition provides independent
supervision for Class A and Class “B” FACP NAC circuits. In the
event of circuit trouble, the FACP will be notied via the POWERPATH
steered input (IN1 or IN2). In addition there are two sets of trouble
reporting terminals, one used for AC power loss reporting and the
other for all troubles. The AC power loss reporting, on the common
trouble terminals and on IN1 or IN2, can be delayed for either 30
seconds or 170 minutes. The AC power loss terminals will always
report the trouble within 1 second after loss of AC power.
PS-6
Approvals
• Approvals Include: UL Standard 864, 1481, California State
Fire Marshal (CSFM), Factory Mutual (FM)
• Compliant with NFPA 72
Inputs
• 120VAC, 50/60Hz, 4.25 Amps (PS-6/8) and 5.32 Amps
(PS-8) Operating Power in Alarm
• 240VAC, 60Hz, 2.42 Amps (PS-6E and 3.22 Amps (PS-8E)
Operating Power in Alarm
• 24VDC Battery Backup Connection
Two (2), 12V or 24V NAC Initiating Circuits (8-33V at 5mA)
FWR or DC
Two (2) “Dry Contact initiating Circuits
• Accepts two (2) Class A or two (2) Class “B” circuit inputs
• Built in battery charger for sealed lead acid or gel type
batteries
Outputs
• NAC outputs are 24VDC, 3.0 Amps each, power limited
• 8 Amps on PS-8 and 6 Amps on the PS-6 total alarm current
...Features continued on next page
U
L
®
PS-8
Notication
The PS-6 and PS-8 Power Supplies are UL Listed under UL
Standard 864, 9th Edition to be used with any 24 volt Listed
Regulated notification appliances. They include the capability
to synchronize Wheelock strobes and horns and to silence the
horn signal when horn/strobes are operating on two wires.
PS-EXP

Summary of content (4 pages)