Cut Sheet

1P
1315
www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright
©
2013 Eaton’s Crouse-Hinds Business
Arktite
®
Heavy Duty Circuit
Breaking
§
Plugs and Receptacles
Industrial Heavy Duty Non-hazardous Areas
NEMA 4 Watertight
The mating plug has a cast groove
located on the outside of the plug
sleeve. This groove lines up with the
raised rib.
Arktite receptacles have a cast raised
rib located inside the receptacle sleeve.
The location of the rib is in a specific
relationship to the receptacle insulator
that houses the contacts.
Standard Materials:
Metallic receptacle housings, plug and
cord connector bodies – high impact
strength copper-free aluminum
Non-metallic receptacles, plugs and
cord connectors – Krydon
®
fiberglass-
reinforced polyester material
Back boxes: 20, 30, 60, 100, 150 and
200 ampere – cast aluminum; 400
ampere – Feraloy
®
iron alloy
Insulation (metallic products): (2-, 3-,
and 4-pole) 30, 60, 100, 200, 400
ampere – fiberglass-reinforced
polyester; 20, 30 ampere (5-pole) –
melamine
Contacts: pressure, solder, binding
screw – brass; crimp/solder 20, 30, 60,
100 ampere – leaded red brass;
crimp/solder 150, 200, 400 ampere –
telurium copper
Standard Finishes:
Feraloy – electrogalvanized and
aluminum acrylic paint
Aluminum – natural
Krydon fiberglass-reinforced polyester
material – gray
Fiberglass-reinforced polyester
insulation – (red)
Melamine – natural (brown)
Brass – natural
Leaded red brass – electro-tin-plate
Accessories:
Accessories include a variety of angle adapters, panel adapters and back boxes for Arktite
receptacles, see pages 1332–1335.
Included throughout 1P are wire mesh cable grips and protective caps for Arktite plugs.
Typical Installation
§150A, 200A and 400A rated units are for service disconnect use only.
1P
Options:
The following special options are available
from factory by adding the suffix to the
Cat. #:
Description Suffix
Reversed contacts. Receptacle
assembled with plug interior
(exposed contacts), plug
assembled with receptacle
interior (recessed contacts). For
applications where plug is
energized to feed normally
de-energized receptacle. Available
on 30 through 400 ampere units...
S22
Special polarity. For use where
two or more receptacles of the
same ampere rating, style and
number of poles are to be
installed in the same area for use
on different voltages and/or
frequencies. Prevents insertion of
a plug in a receptacle with
different electrical rating.
Available on 20 through 400 ampere
units as follows:
Receptacle interior rotated 22
1
/2°
to right and plug changed to
match (see photo to right)..............
S4
Corro-free
epoxy powder finish
for added corrosion resistance......
S752