Spec Sheet

This warranty should be registered on our web-site
www.cooperandhunter.us within 60 days of installation.
The warranty is only valid when installed by a Licensed HVAC
Technician. A warranty period of Seven (7) years on compressor
to the original registered end-user. A warranty period of Five (5)
years on all parts to the original registered end user. Warranty
applies only to products remaining in their original installation
location.
GENERAL FEATURES
Golden n and indoor
Heat pump units can heat & cool up to 5 zones
Turbo Operation
Auto-Restart
Self Diagnosis Function
Multi speed fan
Auto protection
COMPATIBILITY
Connect 5 multiple style indoor units:
Wall mounted: 9K/12K/18K/24K
Cassette: 9K/12K/18K/24K
Console: 9K/12K/18K/24K
Floor & Ceiling: 9K/12K/18K/24K
OUTDOOR SPECIFICATION
Air ow 4500 CFM
Noise Level 64 dB(A)
Dimension (W*D*H) 37.48x16.34x52.48 in
Net/Gross weight 238.32/269.84 lb
Refrigerant type R410A/162 oz
Refrigerant precharge 125 ft
Additional charge for each ft 0.16 oz for 1/4" liquid pipe
0.32 oz for 3/8" liquid pipe
PERFORMANCE AND EFFICIENCY
Cooling Heating
48,000 Btu/h 49,000 Btu/h
SEER 21.5 HSPF4/HSPF5 10.3/8.6
EER 11.6 COP 3.59
OPERATION TEMPERATURE RANGE
Ambient temperature
cooling heating
-22~122 -22~86
ELECTRICAL
Power supply 208-230V/ 60Hz, 1Ph
MCA 35 A
MFA 50 A
MCA: Minimum Circuit Ampacity MFA: Max. fuse A
PIPING
Refrigerant piping Liquid/Gas side 5x1/4"/3x3/8"+2x1/2"
Max. length for all rooms 262 ft
Max. length for one indoor unit 115 ft
Max. height dierence between indoor and outdoor unit 49 ft
Max. height dierence between indoor units 33 ft
WIRING
Connection wiring 16AWG*4 Stranded, unshielded
SUBMITTAL DATA SHEET CH-HYP48MSPH-230VO (OUTDOOR UNIT)
Job Name: ................................................................................................................................... Date: ...........................................................................................................................................
Lacation: ..................................................................................................................................... Approval: ....................................................................................................................................
Engineer:..................................................................................................................................... Construction: ...............................................................................................................................
Submitted to: .............................................................................................................................. Unit #: .........................................................................................................................................
Submitted by: ............................................................................................................................. Drawing #: ..................................................................................................................................
Reference: ...................................................................................................................................
SOPHIA Hyper
SPLIT AIR CONDITIONER WITH HEAT PUMP

Summary of content (2 pages)