INDOOR SPECIFICATION
Air ow (Hi/Mi/Lo) 559/365/306 CFM
Sound Preassure level (Hi/Mi/Lo) 43/38/32 dB(A)
Dimension (WxDxH) 42.52x8.90x13.19 in
Net/Gross weight 29.1/37.0 Lbs
OUTDOOR SPECIFICATION
Air ow 1470 CFM
Sound Preassure level 61 dB(A)
Dimension (WxDxH) 33.27x14.29x27.64 in
Net/Gross weight 101.0/108.2 Lbs
Refrigerant type R410A
Refrigerant precharge 25 ft
Additional charge for each ft 0.16 oz
Job Name:_________________________________________________________________________
Location:________________________________________________________________________
Engineer:______________________________________________________________________
Submitted to:_____________________________________________________________________
Submitted by:_____________________________________________________________________
Reference:_________________________________________________________________________
Date:______________________________________________________________________________
Approval:__________________________________________________________________________
Сonstruction:______________________________________________________________________
Unit #:_____________________________________________________________________________
Drawing #:_________________________________________________________________________
EFFICIENCY
Cooling Heating
SEER 20.8 HSPF4/HSPF5 10/8
EER 13 COP 3.36
SYSTEM PERFORMANCE
Cooling
Capacity 18,000 Btu/h
Input 1384 W
Rated current 6.01 A
Heating
Capacity 18,000 Btu/h
Input 1570 W
Rated current 6.82 A
OPERATION TEMPERATURE RANGE
Indoor Outdoor
cooling heating cooling heating
62 – 90
o
F 32 – 86
o
F -13 – 122
o
F -13 – 86
o
F
ELECTRICAL
Power supply 208-230V / 60Hz, 1Ph
MCA 15 A
MOCP 23,5 A
MFA 20 A
Compressor Type ROTARY
Compressor RLA 10 A
MCA: Minimum Circuit Ampacity; MFA: Max. fuse amps;
MOCP: maximum overcurrent protetive device; RLA: Rated load amps.
PIPING
Refrigerant piping Liquid side/ Gas side 1/4" - 1/2" in
Max. refrigerant pipe length 98 ft
Max. dierence in level 66 ft
WIRING
Connection wiring 16 AWG/4
Power supply wiring 14 AWG/3
SOPHIA
WALL-MOUNTED SERIES
SPLIT AIR CONDITIONER WITH HEAT PUMP
• WiFi Ready
• Mute Operation
• Silver ion Filter
• Anti Cold Air
• Sleep Mode
• Cold Catalyst Filter
• 12 Grades Indoor Fan Speeds
• Self Diagnosis Function
• Two-way Draining Connection
• Indoor and Outdoor
Anticorrosive Coating GoldFin
• Two Direction Airow
• Double Level Air Flaps
• High Density Filter
• Turbo Operation
• Refrigerant Leakege Detect
GENERAL FEATURES
This warranty should be registered on our the web-site www.cooperandhunter.us
within 60 days of installation.
The warranty is only valid when installed by a Licensed HVAC Technician. A war-
ranty period of Seven (7) years on compressor to the original registered end-user.
A warranty period of Five (5) years on all parts to the original registered end user.