Installation Manual

Page 33
DOUBLE CHECK PIPE CONNECTIONS
During operation, the pressure of the
refrigerant circuit will increase. This may
reveal leaks that were not present during your
initial leak check. Take time during the test
run to double-check that all refrigerant pipe
connection points do not have leaks. Refer to the
Gas Leak Check section for instructions.
5. After the test run is successfully complete
and you conrm that all checks points in the
List of Checks to Perform have PASSED, do the
following:
a. Using the remote control, return the unit to
the normal operating temperature.
b. Using insulation tape, wrap the indoor
refrigerant pipe connections that you
left uncovered during the indoor unit
installation process.
IF AMBIENT TEMPERATURE IS BELOW 63°F
(17°C)
You can’t use the remote control to turn
on the COOL function when the ambient
temperature is below 63°F (17°C). In this instance,
you can use the MANUAL CONTROL button
to test the COOL function.
1. Lift the front panel of the indoor unit and
raise it until it clicks in place.
2. The MANUAL CONTROL button is located
on the right-hand side of the unit. Press it 2
times to select the COOL function. See Fig.
8.1.
3. Perform the test run as normal.
Fig. 8.1
Test Run
Manual control button