Instruction Manual
‘RESET’ ‘RESET’ “RESET2” 
then The 
Measured 
Value 
Press the ‘RESET’ the button two times. display will momentarily 
show “RESET2” and then will display the currently measured 
values. 
NOTE: If after zeroing the display with RDF OF, the reading again drifts from zero, the required offset value is the 
sum of the current RDG OF value and the current converted offset value. The examples below illustrate the 
calculation of required offset values when using an independent decimal. If you are using an active decimal point, 
the current converted offset value is simply the negative value of the display reading. 
Example 1: You use a RDG OF value of –1.0000 to zero the meter. The next morning, the meter displays 00.0008 
at zero input; you need to rezero. The current count value is 000008; shifting this value to the left of the decimal 
makes it 08.0000, and making the value negative makes it –8.0000. The required RDG OF value is the sum of the 
current RDG OF value (–1.0000) and the current converted offset value (–8.0000): 
–1.0000 + –8.0000 = –9.0000 
Example: You use a RDG OF value of –1.0000 to zero the meter. The next morning, the meter displays –0.0008 at 
zero input; you need to rezero. The current count value is –00008; shifting this value to the left of the decimal 
makes it –8.0000, and making the value positive makes it 08.0000. The required RDG OF value is sum of the 
current RDG OF value (–1.0000) and the current converted offset value (08.0000): 
–1.0000 + 08.0000 = 07.0000 
If you require further configuration(s) for your specific application, refer to Sections 9 through 21. 
NOTE: Should you receive an error code of any kind while configuring your meter, refer to Section 17 - 
Troubleshooting -Display Messages and Troubleshooting Guide. 
8.4 Scaling Your Meter Without Connecting A Sensor Using Calculated Values 
Your meter can be scaled without connecting a sensor and taking measured values using Input Scale and Offset 
(“IN.SC.OF”). 
The typical configuration and scaling of your meter is a 0-100 mVdc input with a display equal to 0 to 100000. If 
your meter has not been rescaled and your input is 4-20 mAdc, you can use the factory scaling “0” as your 
“INPUT1” and “100000” as your “INPUT2” and proceed with the step-by-step procedure in Section 8.4.1. 
If you need to change your input signal, you must rescale your meter as described in the following steps: 
8.4.1 Preparing Your Meter For Scaling With Input Scale And Offset 
If you are changing your input signal you must follow the instructions for installing the correct jumper positions as 
described in Section 6 and the sensor connections as described in Section 7. 
WARNING: Do not connect your AC meter power until all input jumpers and sensor input connections are 
completed. Failure to do so could result in damage to your sensor and/or the meter. 
The following procedure will direct you step by step in preparing your meter for rescaling using Input Scale and 
Offset (“IN.SC.OF”). 
NOTE: The following procedure will scale your meter to display in microvolts and insure that your final scaling is as 
accurate as possible. 
CF 67  26  M1291/N/0403 11279ML-02 Rev. A 










