Instruction Manual
“INP.1=1”  50 Hz 
Read Rate: 
“INP.2=0”  Slow 
“INP.2=1”  Fast 
Input Voltage: 
“INP.3=0”
  Unipolar 
“INP.3=1”  Bipolar 
Transmitter Type: 
“INP.4=0”
  No Transmitter 
“INP.4=1”  Not used 
“INP.4=2” Not used 
“INP.4=3” Not used 
 Bridge Mode: 
“INP.5=0”
 Normal Operation 
“INP.5=1”  Setpoint 1 value would be lower overload limit and 
Setpoint 2 value would be upper overload limit. 
“INP.6=0” Disabled 
“INP.6=1” Enabled 
  Type of Reading: 
“INP.7=0” Non Ratiometric 
“INP.7=1” Ratiometric 
* The ‘MIN’ button allows you to sequence through INPUT 1, INPUT 2, INPUT 3, INPUT 4, INPUT 5, INPUT 6, and 
INPUT 7. 
The ‘MAX’ button allows you to select the “0” or “1” state for each “INP” condition. 
The ‘MENU’ button stores the selected values for all “IN CNF” condition(s) changed and advances the meter to 
“IN.SC.OF”. Do not press the ‘MENU’ button after each change within the submenu or the meter will advance to 
the next menu item. 
Every underlined “0” or “1” state is the factory preset value. 
9.2.5 IN.SC.OF (Input Scale And Offset) 
Refer to Section 8 for a detailed discussion of this feature. 
Input scale and offset is typically used when you want to scale your meter (using two input data points): 
MENU 
BUTTON 
MAIN MENU 
MIN/MAX * 
BUTTON SUB 
MENU 1 
MIN/MAX/MENU ** 
BUTTON 
SUB MENU 2 
DESCRIPTION 
    INPUT SCALE OFFSET 
    Input scale and offset in 2-Coordinate Format 
INPUT 1    Item #1 of Coordinate #1. 
 000000. (“000000.”)
  Enter the first value displayed by the meter. 
READ 1    Item #2 of Coordinate #1. 
 000000. (“000000.”)
  Enter first desired value. 
INPUT 2    Item #1 of Coordinate #2. 
 000000. (“100000.”)  Enter the second value displayed by the meter. 
“IN.SC.OF”: 
READ 2    Item #2 of Coordinate #2. 
CF 67  37  M1291/N/0403 11279ML-02 Rev. A 










