Instruction Manual
  Alarm 2 open-collector or relay output Active ON or OFF: 
“ALC.5=0”
 On 
“ALC.5=1” Off 
  Filtered/unfiltered reading compared with Alarm 2 (Setpoint 4) value:
“ALC.6=0” Unfiltered 
“ALC.6=1” Filtered 
  Alarms 1 & 2 (Setpoints 3 & 4) action and LEDs: 
“ALC.7=0” Enabled 
“ALC.7=1” Disabled 
  Alarm reset at P2-11 connector: 
“ALC.8=0”
 Disabled 
“ALC.8=1” Enabled 
* The ‘MIN’ button allows you to sequence through ALC.1, ALC.2, ALC.3, ALC.4, ALC.5, ALC.6, ALC.7 and ALC.8. 
The ‘MAX’ button allows you to select the “0” or “1” state for each “ALC” condition. 
The ‘MENU’ button stores the selected values for each “ALC” condition changed and advances the meter to the 
next configuration (“AL FNC”). 
Every underlined “0” or “1” is the factory preset value. 
9.2.12 AL FNC (Alarm Function) 
Refer to Section 10 for an in-depth discussion of these features. Alarm function is used to select: 
•  whether the alarms are used in the process, high-deviation, low-deviation or band deviation modes [ALF.1 & 
ALF.3] 
•  whether or not to latch the alarms [ALF.2 & ALF.4] 
MENU BUTTON 
MAIN MENU 
MIN/MAX/MENU * 
BUTTON SUB MENU 
DESCRIPTION 
ALARMS 1 & 2 FUNCTION: 
Alarm 1 State: 
“ALF.1=0”
  Process Mode 
“ALF.1=1”  High Deviation Mode 
“ALF.1=2”  Low Deviation Mode 
“ALF.1=3”  Band Deviation Mode 
Alarm 1 Latch Action: 
“ALF.2=0”
  Unlatched 
“ALF.2=1” Latched 
  Alarm 2 State: 
“ALF.3=0”
  Process Mode. Process Mode means the deadband is equally 
above and below the setpoint. 
“ALF.3=1” High Deviation Mode 
“ALF.3=2” Low Deviation Mode 
“ALF.3=3”  Band Deviation Mode 
  Alarm 2 Latch Action: 
“ALF.4=0” Unlatched 
“AL FNC”: 
“ALF.4=1” Latched 
* The ‘MIN’ button allows you to sequence through ALF.1, ALF.2, ALF.3 and ALF.4. 
The ‘MAX’ button allows you to select the “0”, “1”, “2”, or “3” state for each “ALF” condition. 
CF 67  42  M1291/N/0403 11279ML-02 Rev. A 










