The ‘MAX’ button allows you to select the “0”, “1”, “2”, “3”, “4” or “5” state for each “OUT” condition. 
The ‘MENU’ button stores the selected values for each “OUT” condition changed and advances the meter to the 
next configuration (“OT.SC.OF”). 
Every underlined item is the factory preset value. 
9.2.17 OT.SC.OF (Output Scale And Offset) 
Output scale and offset is used to calibrate your optional analog output to correspond to the engineering units you 
desire. 
MENU BUTTON 
MAIN MENU 
MIN/MAX/* 
BUTTON SUB 
MENU 1 
MIN/MAX MENU ** 
BUTTON 
SUB MENU 2 
DESCRIPTION 
  OUTPUT SCALE 
AND OFFSET 
READ 1    Item #1 of Coordinate #1. 
 000000. (“000000.”)
Enter the first value displayed by the meter. 
OUTPT1    Item #2 of Coordinate #1. 
 00.0000 (“04.0000”)
Enter first desired output value. 
READ 2    Item #1 of Coordinate #2. 
 000000. (“100000.”)
Enter the second value displayed by the meter. 
OUTPT2    Item #2 of Coordinate #2. 
“OT.SC.OF”: 
 00.0000 (“20.0000”)
  Enter second desired output value. 
* The ‘MIN’ button allows you to sequence through “READ 1”, “OUTPT1”, “READ 2”, and “OUTPT2” headings. 
The ‘MAX’ button sends you to the value corresponding to “READ 1”, “OUTPT1”, “READ 2”, and “OUTPT2” so you 
can change it (go to the SUB MENU 2 item). 
** The ‘MIN’ button allows you to step through the digits of the applicable number being changed. 
The ‘MAX’ button changes the value of the digit to be displayed. 
The ‘MENU’ button stores the selected values for each input required in “OT.SC.OF”. After the last value (“READ 
2”) has been entered and the ‘MENU’ button is pressed, the meter display will advance to “BAUD”. 
Every underlined item is the factory preset value. 
9.2.18 BAUD (Baud Rate) 
Baud is used to select the baud rate for communication via the optional RS-232 or RS-485 communications boards. 
The choices are 300, 600, 1200, 2400, 4800, 9600, and 19200. 
MENU BUTTON 
MAIN MENU 
MIN/MAX/MENU * 
BUTTON SUB MENU 
DESCRIPTION 
BAUD RATE 
“00300” 
“00600”  Select baud rate for communications via RS-232 or RS-485 
“01200” 
“02400” 
“04800” 
“09600” 
“BAUD”: 
“19200” 
* Press the ‘MIN’ button to show “00300”, “00600”, “01200”, “02400”, “04800”, “09600”, or “19200”. 