Instruction Manual
16.11 Print Command And/Or Reset Of Alarms (PIN 11) 
Grounding this pin to P2-7 when “BUS.8=1” has been programmed will initiate a meter printout via serial 
communications in the format previously selected. If “ALC.8=1” it causes the alarm latches to reset. 
16.12 Nonstandard RX (PIN 12) And Nonstandard TX (PIN 13) 
These two pins allow digital communications with the meter using 5 V CMOS logic levels and RS-232 protocols and 
format. This access is normally reserved for specialized equipment communication in a calibration lab or at the 
factory. 
16.13 Push to CAL (PIN 14) 
See Section 16.6. 
16.14 +V EXT (PIN 15) 
This is the pin on which to bring in isolated external 5 to 30 V to power the snubbing diodes of the four 
setpoint/alarm open-collector transistors. 
16.15 SP1 (PIN 16) 
The open-collector of the first setpoint transistor (can carry 150 mA). 
16.16 SP2 (PIN 17) 
The open-collector of the second setpoint transistor (can carry 150 mA). 
16.17 AL1 (PIN 18) 
The open-collector of the third setpoint (first alarm) transistor (can carry 150 mA). 
16.18 AL2 (PIN 19) 
The open-collector of the fourth setpoint (second alarm) transistor (can carry 150 mA). 
16.19 RTN EXT (PIN 20) 
This is the return to the external ground (P2-20) of the external power for the setpoint transistors and snubbing 
diodes brought in on P2-15, 16, 17, 18 and 19. Figure 16-2 shows an example of a circuit using an external relay 
with SP1 (Setpoint 1). If a solid-state relay is used, delete connection to Pin 15. 
Figure 16-2. Connection of External Power for Setpoint Transistors 
17.0 TROUBLESHOOTING - DISPLAY MESSAGES AND TROUBLESHOOTING 
GUIDE 
A flashing alpha-numeric message in the display generally indicates an incorrect combination of jumpers and/or 
configuration values. 
CF 67  67  M1291/N/0403 11279ML-02 Rev. A 










