Zone Operational Mode Parameter Details:
First On/Last Off:
If the zone is OFF, switched loads in the zone will respond ON when any command level other than 0% is received. If the zone is ON,
switched loads within the zone will turn OFF when the zone reaches a 0% (OFF) light level.
First On/First Off:
If the zone is OFF, switched loads in the zone will respond ON when any command level other than 0% is received. If the zone is ON,
switched loads in the zone will turn OFF when a command lower than the current zone level is received.
Last On/First Off:
If the zone is OFF, switched loads in the zone will respond ON when any command at or above the defined maximum level (high end trim)
is received. If the zone is ON, switched loads in the zone will turn OFF when a command lower than the current zone level is received.
Last On/Last Off:
If the zone is OFF, switched loads in the zone will respond ON when any command at or above the defined maximum level (high end trim)
is received. If the zone is ON, switched loads in the zone will turn OFF when the zone reaches a 0% (OFF) light level.