Programming Manual

68
WaveLinx User Manual
www.eaton.com/wavelinx
Step 6: Review the changes to verify that all desired occupancy sets have been associated. Note that the occupancy set screen should show
the quantity of sets associated. In this example, any time occupancy is detected by occupancy sets A, B, or C, the occupancy signal will be
forwarded to trigger occupancy set D.
Review changes to verify all necessary
occupancy sets are associated
Application Example 1: Open Office
In this example, an open office has been segmented into distinct occupancy control zones. The walkway path has also been placed in a
unique control zone. The walkway path zone should turn ON if anyone enters the space and should remain ON if there are occupants in any
of the controlled zones. Unique occupancy sets have been programmed in the area for each of the zones shown.
Zone A Zone B Zone C
Zone D
(walkways)
Associations are made between the occupancy sets controlling zone A, B, and C, to the walkway occupancy set D. (Remember, the general
rule is to modify the occupancy set that needs to receive signals from other occupancy sets.) In this example, occupancy set D is associated
with the other sets.