Programming Manual

82
WaveLinx User Manual
www.eaton.com/wavelinx
Step 1: Verify that light levels are optimal for calibration. First, turn OFF the electric lighting in the space, and then verify with a light meter
at the work surface that the reading with daylight alone is within 50% to 75% of the desired target light level. If the light level is too high or
too low, return at a time when the daylight level is within this optimal range. (For example, if the desired light level at the work surface is 500
lux, the reading with electric lighting OFF should be between 250 to 375 lux for best results.)
Step 2: Open the WaveLinx Mobile Application and establish a connection with the Wireless Area Controller as the administrator user.
Step 3: In the areas list, select the area to calibrate.
•
Step 4: Using a wallstation, turn ON the controlled lighting and raise the light level to the highest output.
Step 5: If multiple ceiling sensors are within the area, only one will be used for daylighting. In the mobile application area screen, identify the
correct sensor by shining a flashlight into the lens of the sensor for 3 to 4 seconds. The sensor icon should flash or pulse. Make note of the
identified sensor’s name/descriptor.