Cut Sheet

Figure 1. Three-phase pad-mounted compartmental type transformer.
LOW-
VOLTAGE
BUSHING
SUPPORT
SILL
Suitable for skidding,
rolling, and jacking
5-position tap changer
Ground pad and strap for x
0
Parking stand
Liquid level gauge
Nameplate
laser-scribed anodized aluminum
Removable cabinet
walls
Drip shield
Type Three Phase, 50 or 60 Hz, 65 ºC Rise
(55 ºC, 55/65 ºC), 65/75 °C, 75 °C
Fluid Type Mineral oil or Envirotemp™FR3™ fluid
Coil Configuration 2-winding or 4-winding or 3-winding (Low-High-Low), 3-winding (Low-Low-High)
Size 45 – 10,000 kVA
Primary Voltage 2,400 – 46,000 V
Secondary Voltage 208Y/120 V to 14,400 V
Specialty Designs
Inverter/Rectifier Bridge
K-Factor (up to K-19)
Vacuum Fault Interrupter (VFI)
UL
®
Listed & Labeled and Classified
Factory Mutual (FM) Approved
®
Solar/Wind Designs
Differential Protection
Seismic Applications (including OSHPD)
Hardened Data Center
Table 1. Product Scope
Bay-O-Net fusing
LOW-VOLTAGE
BUSHING
Low-voltage
molded epoxy
bushings with
NEMA
®
spades
LOADBREAK SWITCH
2
Catalog Data CA202003EN
Effective April 2016
Three-phase pad-mounted compartmental type transformer
www.eaton.com/cooperpowerseries
HIGH-VOLTAGE BUSHING