Installation Manual
Installation procedure
Mounting requirements
Sidewall-mounted with the internal stud end completely 
immersed under oil or SF
6
. All parts should be inspected 
for damage before using. Clamping studs must be welded 
around the bushing hole to accommodate either a 3-hole or 
4-hole clamp. Install the gasket over the bushing assembly 
through the tank hole and place the clamp* over the weld-
ed tank studs against the bushing flange. Install a plated 
lock-washer and nut onto each stud and tighten to recom-
mended torque. The Tri-Clamp well should have a plated 
flatwasher, lock washer and nut. Tighten to recommended 
torque. Connect internal lead to the internal bushing stud 
using recommended torque and procedures. See Figure 5.
*One-piece molded (Tri-Clamp) bushing well does not require a 
clamp.
Table 2.  Tank Hole (Ref. Figure 4) 4-Stud Square Clamp
kV Class Description
"A"** Tank 
Hole Size (Dia.)
"B" 
C-C Stud Spacing
15 & 25
200 A Bushing 
Well with a 2.19" 
Diameter Shank
2.25"
(57 mm)
2.75", 3.00", or 
3.25" 
(70, 76, or 83 mm)
15, 25 
& 35
200 A Bushing 
Well with a 2.50" 
Diameter Shank
2.56"
(65 mm)
2.75", 3.00", or 
3.25" 
(70, 76, or 83 mm)
35
200 A Loadbreak 3Ø 2.75"
(70 mm)
3.87"
(98 mm)
15, 25 
& 35
600 A Deadbreak
2.56"
(65 mm)
3.43"
(87 mm)
Figure 4.  Tank mounting hole for 3- and 4-hole stud 
configuration.
“A” “A”
“B”
4 STUD
3 STUD
MOUNTING 
STUDS
“C” 
BOLT CIRCLE
DIAMETER
30TYP.
4.7" (120 mm) MIN. DIA. EXTERIOR MOUNTING SURFACE BETWEEN THE 
DOTTED LINE AND TANK HOLE TO BE FLAT AND CLEAR OF 
SURFACE OBSTRUCTIONS, SUCH AS WELD SPLATTER.
120 TYP.
Table 1.  Electrical Ratings
kV
Class Description
Voltage Withstand
Continuous
Current
Rating*
Impulse
Withstand
kV BIL
Minimum
Corona
Voltage
Maximum
Rating
Voltage
(RMS)
AC 60 Hz
1 Min RMS
DC
15 Min P-G P-P
15, 25, & 28 200 A Bushing Well (HTN and epoxy) 40 78 200 A 125 21.5 16.2 –
35 Tri-Clamp, 200 A Bushing Well 50 103 200 A 150 26 21.1 –
35 1-Pc, 200 A Loadbreak Bushing 50 103 200 A 150 26 21.1 36.6
15/25 1-Pc, 600 A Deadbreak Bushing 40 78 600/900 A 125 19 15.2 –
35 1-Pc, 600 A Deadbreak Bushing 50 103 600/900 A 150 26 21.1 –
35 1-Pc, 600 A Deadbreak Bushing 70 114 600/900 A 200 26 21.1 –
* 600 A with aluminum components and 900 A with copper components.
Figure 5.  High voltage bushing (all, including bushing 
well) internal lead training. (Bushing shown-35 kV, 600 A 
deadbreak.)
BUS BAR: 
No sharp edges 
or corners. 
Should be 
directed parallel 
to or away from 
tank wall.
GASKET
TANK 
WALL
TIGHTENING 
NUTS 
(1 OR 2)
SPACER NUT
HIGH VOLTAGE LEAD AND TERMINAL:
No sharp edges or burrs. Should be directed 
parallel to or away from tank wall.
2
High-voltage primary bushings installation instructions S800-35-2 November 2013 www.cooperpower.com