Specification
www.cooperwiringdevices.com
Modular Receptacles
Specification & Performance Data
Project Name: Prepared By:
Project Number: Date:
Catalog Number: Type:
2-ALMSPSH8-0311
Device Type
Specification Grade GFCI 15A & 20A:
VGF__MOD and VGF__F__MOD Series
ArrowLink: MCR125_, MCR250_, MCR300_ Series
Specification Grade Tamper Resistant & Weather Resistant
Duplex GFCI 15A & 20A: TRVGF__MOD, TRVGF__F__MOD,
WRVGF__MOD, TWRVGF__MOD Series
ArrowLink: MCR125_, MCR250_, MCR300_ Series
Wiring
Type
Base Device
Back & side wire Back & side wire
ArrowLink
Integral wire leads, crimped & resistance welded Integral wire leads, crimped & resistance welded
ArrowLink SPD
Backwire feed through Backwire feed through
Testing & Code
Compliance
Base Device
• cULus Listed to UL 498 and UL 943, file no. E60120
• cULus Listed to UL 498 and UL 943, file no. E60120
• Meets all UL 943 (GFCI), UL 498 (Receptacles) and applicable
CSA requirements
• Meets all UL 943 (GFCI), UL 498 (Receptacles) and applicable
CSA requirements
• NOM certified • NOM certified
ArrowLink
• Plug & connector cULus Listed to to UL 2459, file no.
E325188
• Plug & connector cULus Listed to to UL 2459, file no.
E325188
Combined
• cULus Listed wiring assembly, UL file no. E326691
• cULus Listed wiring assembly, UL file no. E326691
Specifications:
Environmental
Base
Device
Flammability
Meets UL 94 requirements; V2 rated Meets UL 94 requirements; V2 rated
Temperature Rating
-35ºC to 66ºC (-31ºF to 150.8ºF) -35ºC to 66ºC (-31ºF to 150.8ºF)
ArrowLink
Flammability
Meets UL 94 requirements; V2 rated Meets UL 94 requirements; V2 rated
Temperature Rating
-35ºC to 66ºC (-31ºF to 150.8ºF) -35ºC to 66ºC (-31ºF to 150.8ºF)
Specifications:
Electrical
Base Device
Dielectric Voltage
Withstands 2000V per UL 498 Voltage: withstands 2000V per UL 498
Current Interrupting
Yes, at full-rated current Yes, at full-rated current
Temperature Rise
Temperature Rise: max. 30ºC (86°F) after 100 cycles of overload
@ 150% of rated current (DC)
Max. 30ºC (86°F) after 100 cycles of overload @ 150% of rated
current (DC)
Trip Time
0.025 seconds (Class A) 0.025 seconds (Class A)
Frequency
60 Hz; Voltage: 125V; Amperage: 15A/20A 20A Feed Through 60 Hz; Voltage: 125V; Amperage: 15A/20A 20A Feed Through
Short Circuit Testing
Meets and exceeds 10 kA Meets and exceeds 10 kA
Maximum Interrupting
Capacity
20 Amps 20 Amps
ArrowLink
Max. Working Voltage
300V/AC 300V/AC
Max. Continuous Current
20A 20A
Overload
52.5A/AC for 10 cycles 52.5A/AC for 10 cycles
Dielectric Voltage
Withstands 1600V per UL 2459 Withstands 1600V per UL 2459
Current Interrupting
Limited cycles at full-rated current Limited cycles at full-rated current
Temperature Rise
Max. 50ºC (122°F) while conducting 35A after 10 cycles of
overload @ 52.5A/AC
Max. 50ºC (122°F) while conducting 35A after 10 cycles of
overload @ 52.5A/AC
Specifications:
Mechanical
Base Device Terminal
Accommodation
#14 - #10 AWG #14 - #10 AWG
ArrowLink Wire Leads
#12 AWG
#12 AWG
ArrowLink SPD Screw
Terminals
Accepts #12-#14 stranded and solid wire Accepts #12-#14 stranded and solid wire
ArrowLink SPD Ground
Integral THHN #12 AWG 6" lead with ring terminal and #10
ground screw
Integral THHN #12 AWG 6" lead with ring terminal and #10
ground screw
Voltage Ratings
Permanently marked on device Permanently marked on device
Specifications:
Screw Terminal
Guards
ArrowLink Models Only
Material: UL recognized insulating material
Dielectric Strength: 2,000V min
HWI Rating: 4 min.
Relative temperature index, electrical: 80ºC (176ºF)
Flammability: V0 (UL 94)
Material: UL recognized insulating material
Dielectric Strength: 2,000V min
HWI Rating: 4 min.
Relative temperature index, electrical: 80ºC (176ºF)
Flammability: V0 (UL 94)
Materials:
Base Device
Top Housing
Thermoplastic, nylon
Thermoplastic, nylon; except WR: nylon 6/6
Bottom Housing
PVC
PVC
Strap
0.047" thick steel, zinc plated
0.047" thick steel, zinc plated; WR & TWR: nickel-plated
Line Contacts
0.030" thick brass
0.030" thick brass
Terminal & Ground
Screws
#8-32 steel, brass plated; neutral screw nickel plated, ground
screw green
Terminal: Brass/nickel-plated steel; WR & TWR brass/nickel-
plated stainless steel; Ground: ground screw green on all models,
WR and TWR stainless steel
Terminal Clamps
0.070" thick steel
Brass-plated steel; WR & TWR nickel-plated steel
ArrowLink
Housing
Polycarbonate
Polycarbonate
Contacts
Copper alloy
Copper alloy
Wire Leads
Solid or stranded THHN #12 AWG
Solid or stranded THHN #12 AWG
ArrowLink
SPD
Housing
Polycarbonate Polycarbonate
Contacts
Copper alloy Copper alloy
2-Pole, 3-Wire Grounding
15A, 125V/AC; 20A, 125V/AC
NEMA 5-15, 5-20
Specification Grade
Ground Fault Circuit
Interrupter Receptacles
Specifications subject to change without notice.