Instructions / Assembly
7. Connect the wires (choose A or B) ... only after reading other side completely
8. Test your work
Why perform this test?
If you miswire the GFCI, it may not prevent personal injury or death due to a ground fault
(electric shock).
Upon initial installation, if you mistakenly connect the LINE wires
to the LOAD terminals, this Cooper GFCI will not be able to be
reset, and will therefore not provide power to it’s receptacle face
or load terminals.
Procedure:
(a) Turn the power ON at the service panel. Press the RESET
button fully. Plug a lamp or radio into the GFCI (and leave it
plugged-in) to verify that the power is ON. If there is no power, go
to Troubleshooting.
(b) Press the TEST button in order to trip the device. This should
stop the flow of electricity, making the radio or lamp shut OFF and
the yellow Correct Wiring/Trip Indicator come on. To restore
power, press the RESET button.
(c) If you installed your GFCI using step 7B, now plug a lamp or
radio into surrounding receptacles to see which one(s), in addition
to the GFCI, lost power when you press the TEST button. Do not
plug life saving devices into any receptacles that lost power.
Place a “GFCI Protected” sticker on every receptacle that lost
power.
(d) Press the TEST button (then RESET button) every month to
assure proper operation.
(e) Note that this Cooper GFCI is shipped in the Tripped state and
cannot be Reset until it is wired correctly and powered from it’s
Line terminals.
(f) Note that the RESET button will pop-out. If the power goes OFF and the correct wiring/trip
indicator stays on, you have installed the GFCI receptacle correctly.
(g) LINE/LOAD reversal will be indicated by the reset button not staying in after being pressed.
Such LINE/LOAD reversal will also be indicated by failure of the Correct Wiring/Trip Indicator
to be on while the GFCI is tripped.
NOTE: If this Cooper Wiring Devices GFCI has tripped and no longer can be
reset, it has reached it’s “End of Life” and will no longer provide power.
Replace with the same model Cooper Wiring Devices GFCI to continue to
provide ground fault protection.
A: One cable (2 or 3 wires) entering the box B: Two cables (4 or 6 wires) entering the box
OR
Grounding connection to
box (if box has a
grounding terminal)
Electrical box
LINE cable brings power to the GFCI
LOAD cable feeds power
to other receptacle(s)
C
able to
switched LOAD
White
Black
Black
Black
Hot to LOAD
LINE
White
Black (LINE)
W
ire Connector
T
his white wire is
HOT only when
used to feed power
to a switch
Connect the LINE cable wires to the LINE terminals:
• The white wire connects to the White terminal (Silver)
• The black wire connects to the Hot terminal (Brass)
Connect the switch leads to the switch controlled LOAD (not GFCI protected, shown
in diagram) using supplied wire connectors:
• One black switch lead connects to the line side black wire.
• The other black lead connects to the Hot side of the LOAD.
• The LOAD must be properly connected to Neutral and grounded.
NOTE: Wiring for switched LOAD shown here is only one of several options. If you are unsure
about any part of these instructions, consult a qualified electrician.
Wire connectors to be used with the following wire combinations (strip wires 3/8”(9.5mm)).
Connect the grounding wire (only if there is a grounding wire):
• For a box with no grounding terminal (diagram not shown): Connect the LINE cable's bare
copper (or green) wire directly to the grounding terminal on the GFCI receptacle
• For a box with a grounding terminal (diagram shown above): Connect a 6-inch bare copper (or
green) 12 or 14 AWG wire to the grounding terminal on the GFCI. Also connect a similar wire to
the grounding terminal on the box. Connect the ends of these wires to the LINE cable's bare
copper (or green) wire using a wire connector. If these wires are already in place, check the
connections.
Complete the installation:
• Fold the wires into the box, keeping the grounding wire away from the White and Hot
terminals. Screw the receptacle to the box and attach the faceplate.
• Go to step 8.
Connect the LINE cable wires to the LINE terminals:
• The white wire connects to the White terminal (Silver)
• The black wire connects to the Hot terminal (Brass)
Connect the LOAD cable wires to the LOAD terminals:
• Remove the yellow sticker to reveal the LOAD terminals
• The white wire connects to the White terminal (Silver)
• The black wire connects to the Hot terminal (Brass)
Connect the switch leads to the switch controlled LOAD (not GFCI protected, shown in
diagram) using supplied wire connectors:
• One black switch lead connects to the line side black wire.
• The other black lead connects to the Hot side of the LOAD.
• The LOAD must be properly connected to Neutral and grounded.
NOTE: Wiring for switched LOAD shown here is only one of several options. If you are unsure
about any part of these instructions, consult a qualified electrician.
Wire connectors to be used with the following wire combinations (strip wires 3/8”(9.5mm)).
Connect the grounding wires (only if there is a grounding wire):
• Connect a 6-inch bare copper (or green) 12 or 14 AWG wire to the grounding terminal on the
GFCI. If the box has a grounding terminal, also connect a similar wire to the grounding terminal
on the box. Connect the ends of these wires to the LINE and LOAD cable's bare copper (or
green) wire using a wire connector. If these wires are already in place, check the connections.
Complete the installation:
• Fold the wires into the box, keeping the grounding wire away from the White and Hot
terminals. Screw the receptacle to the box and attach the faceplate.
• Go to step 8.
TROUBLESHOOTING
Turn the power OFF and check the wire connections against the appropriate wiring
diagram in step 7A or 7B. Make sure that there are no loose wires or loose connections.
Also, it is possible that you reversed the LINE and LOAD connections. Reverse the LINE
and LOAD connections if necessary. Start the test from the beginning of step 8 if you
rewired any connections to the GFCI.
General Information
C
OOPER'S LIMITED 2 YEAR WARRANTY
Cooper Wiring Devices warrants its Ground Fault
Circuit Interrupter (GFCI) to be free of defects in
materials and workmanship in normal use and
service for a period of two years from date of original
purchase. THIS TWO (2) YEAR LIMITED WARRANTY
IS IN LIEU OF ALL OTHER WARRANTIES,
OBLIGATIONS, OR LIABILITIES, EXPRESSED OR
IMPLIED (INCLUDING ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE THAT IS IN DURATION IN EXCESS OF TWO
YEARS FROM THE DATE OF ORIGINAL CONSUMER
PURCHASE). NO AGENT, REPRESENTATIVE, OR
EMPLOYEE OF COOPER WIRING DEVICES HAS
AUTHORITY TO INCREASE OR ALTER THE
OBLIGATIONS OF COOPER WIRING DEVICES UNDER
THIS WARRANTY.
To obtain warranty service for any properly installed
Cooper GFCI that proves defective in normal use send
the defective GFCI prepaid and insured to Quality
Control Dept. Cooper Wiring Devices, 203 Cooper
Circle, Peachtree City, GA 30269.
Cooper Wiring Devices will repair or replace the
defective unit, at its option. Cooper Wiring Devices
will not be responsible under this warranty if
examination shows that the defective condition of
the unit was caused by misuse, abuse, improper
installation, alteration, improper maintenance or
repair of damage in shipment to Cooper Wiring
Devices.
COOPER WIRING DEVICES SHALL HAVE NO
RESPONSIBILITY FOR INSTALLATION OF THE GFCI,
OR FOR ANY PERSONAL INJURY, PROPERTY
DAMAGE, OR ANY SPECIAL, INCIDENTAL,
CONTINGENT, OR CONSEQUENTIAL DAMAGES OF
ANY KIND, RESULTING FROM DEFECTS IN THE GFCI
OR THE FAILURE OF THE PRODUCT TO FUNCTION IN
THE EVENT OF A GROUND FAULT ON ITS PROTECTED
CIRCUIT, OR FOR BREACH OF ANY EXPRESS OR
IMPLIED WARRANTY ON THIS PRODUCT.
THE EXCLUSIVE REMEDY FOR BREACH OF THE
LIMITED WARRANTY CONTAINED HEREIN IS THE
REPAIR OR REPLACEMENT OF THE DEFECTIVE
PRODUCT AT COOPER WIRING DEVICE'S OPTION.
IMPLIED WARRANTIES (IF ANY) INCLUDING, BUT
NOT LIMITED TO IMPLIED WARRANTIES OF
FITNESS FOR A PARTICULAR PURPOSE AND
MERCHANTABILITY, ARE LIMITED IN DURATION TO
A PERIOD ENDING TWO YEARS FROM THE DATE OF
ORIGINAL CONSUMER PURCHASE. IN NO CASE
SHALL COOPER LIABILITY UNDER ANY OTHER
REMEDY PRESCRIBED BY LAW EXCEED THE
PURCHASE PRICE. Some states do not allow the
exclusion or limitation of incidental or consequential
damages or allow disclaimers or modifications of or
limitations on how long an implied warranty lasts, so
the above limitations may not apply to you. This
warranty gives you specific legal rights and you may
also have other rights which vary from state to state.
Read enclosed instructions carefully. If you have any
questions concerning use or care of this product,
please write: Consumer Service Division, Cooper
Wiring Devices, 203 Cooper Circle, Peachtree City,
GA 30269. In Canada: Cooper Wiring Devices, 5925
McLaughlin Road, Mississauga, Ontario, L5R 1B8.
Cable to
switched load
Grounding connection to
box (if box has a
grounding terminal)
Hot to LOAD
LINE
Black
Black (LINE)
Wire Connector
LINE cable brings power to the GFCI
This white wire is HOT
only when used to feed
power to a switch
Black
Electrical box
Yellow sticker
remains in place
to cover the LOAD
terminals
White
About wire connections:
Sidewire:
Backwire:
• Insert bare end fully
• Tighten screw firmly
Clockwise, 2/3 of the
way around screw
Wire
7/8 inch (2.22 cm)
11/16"
(1.75 cm)
2 #14
2 or 3 #16
2 to 5 #18
3 #16 with 1 #18
1 #14 with 1 or 2 #16
2 #16 with 1 or 2 #18
1 #14 with 1 to 3 #18
GFCI ratings:
15A-125V AC GFCI Receptacle
20A feed-through
125V Class A
Switch ratings:
15A max.-120V/AC
1/2 Hp @ 120V, for motor loads of 12 FLA
max. and not to exceed 1/2 Hp.
About wire connections:
Sidewire:
Backwire:
• Insert bare end fully
• Tighten screw firmly
Clockwise, 2/3 of the
way around screw
Wire
7/8 inch (2.22 cm)
11/16"
(1.75 cm)
2 #14
2 or 3 #16
2 to 5 #18
3 #16 with 1 #18
1 #14 with 1 or 2 #16
2 #16 with 1 or 2 #18
1 #14 with 1 to 3 #18