Instructions / Assembly

www.cooperwiringdevices.com2-LCSVSPSH3-0410
Wallbox Lighting Controls
Specification & Performance Data
P
roject Name: Prepared By:
Project Number: Date:
C
atalog Number: Type:
Application
Device Type
SAVANT Occupancy & Vacancy Sensor Dimmers:
OS106D1, VS3106D1 Series
Wiring Type
6" pre-stripped wire leads, #16 AWG
Testing & Code
Compliance
cULus Listed to UL244A & UL1472, file no.
E325082
NOM Certified
California Title 24 Compliant
Specifications:
Environmental
Flammability
Meets UL 94 requirements; V2 rated
Temperature Rating
0ºC to 40ºC (32°F to 104°F)
Specifications:
Electrical
Rating
120V/AC 60Hz, 1/6 HP
Light Intensity Control
Full-range, continuously variable dimming
Dimming Performance
Smooth and continuous Square Law Dimming curve
Solid State Dimming
Surge Protection
Meets ANSI/IEEE Std. C62.41-1980, tested to
withstand voltage surges up to 6000V and current
surges of up to 200A without damage
Radio Frequency
Interference
Designed to reduce interference with radio, audio and
video equipment
Power-failure Memory
Light returns to same level prior to power interruption
Lamp Ratings
Incandescent, Halogen, Magnetic Low-Voltage
Specifications:
Mechanical
Wiring Types
Single-Pole
LED Indicators
Load status indicator, light level & locator
Air-Gap Switch
Meets UL20 & UL1472 for inclusion of visible,
accessible air-gap off switch
Voltage Ratings
Permanently marked on device
Materials:
Top Housing
Polycarbonate
Bottom Housing
Polycarbonate
Strap
Aluminum
Form Factor
Decorator
Finish
Gloss
Specifications subject to
change without notice.
Single-Pole Wiring Diagram, INC/MLV
Single-Pole
600W/VA
I
ncandescent, Halogen, Magnetic Low-Voltage
SAVANT
Sensor Dimmer
Controls
De-Rating Chart
600W Models
1-Gang 2-Gang 3-Gang
Incandescent
600W
max.
600W
max.
600W
max.
Magnetic
Low-Voltage
600VA
max.
600VA
max.
600VA
max.
SAVANT Dimmer Occupancy/Vacancy Sensors use advanced PIR technology to sense the movement of heat-emitting bodies.
Occupancy Sensors provide Auto-ON/Auto-OFF or Manual-ON/Auto-OFF operation while Vacancy Sensors provide Manual-
ON/Auto-OFF operation only (Title 24 2008 Compliant). The sensors automatically turn lights off after a space becomes vacant and
a
preset time delay elapses. Built-in dimmer provides preset full-range dimming of light load. A horizontal dim/bright bar with row of
green LEDs provide intuitive control. Both versions provide Single-Pole (single-location) wiring and work with Incandescent and
Magnetic Low-voltage lighting load types. All sensors are compatible with any decorator-style or decorator screwless wallplate.