1 Way Input / Output Unit - MIO1240
Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting back-box.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according to the diagram below.
Notes:
No addressing of the interface is required. See control panel operation for details.
Standard Connections
WARNING: Segregate mains cable from other connections to this unit. 230 V Relay output is un-
fused. Ensure that the 230 V supply feeding this unit is adequately protected
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor must always be fitted, even if the inputs are unused.
Section 5 - Appendix
Only connected cable screen to its adjacment earth terminal.
The end of line resistor must always be be fitted, even if the spur is unused.
Analogue addressable loop
In
Out
Spur Input
Volt-Free Output
230V rated
5K6
22K
E C N/C N/O
EE---+++