Submittal Sheet
CR38K6E-PFV
HFC, R-407C, 60Hz, 1- Phase, 208/230 V
Air Conditioning
Production Status:
Mechanical
Available for sale to all U.S. customers. Please check with your local Emerson Climate
Technologies Representative for international availability.
Evap(°F)/Cond(°F)
Capacity
(Btu/hr)
Power (Watts):
Current (Amps):
EER (Btu/Wh):
Mass Flow (lbs/hr):
Sound Power (dBA):
Vibration (mils(peak-
Record Date:
45 / 130 45 / 100
35000
3300
47400
2680
16.30 14.15
10.60 17.70
509 589
76 Avg 81 Max
3.6 Avg 4.6 Max
2010-09-01
Number of Cylinders:
2 Displ(in^3/Rev):
Displ(ft^3/hr):Bore Size(in):
Stroke(in):
1.96
0.67
Overall Length (in):
Overall Width (in):
Overall Height (in):
10.23
14.31
9.65
Mounting Length (in):
Mounting Width (in):
Mounting Height (in):
4.05
492.79
7.50
7.50
14.69
Suction Size (in):
Discharge Size (in):
Initial Oil Charge (oz):
Oil Recharge (oz):
Net Weight (lbs):
Internal Free Volume (in^3):
Horse Power:
*Overall compressor height on Copeland Brand Product's specified
mounting grommets.
3/4 Stub
1/2 Stub
43
45
70
Electrical
LRA-High*:
LRA-Half Winding:
LRA Low*:
RLA(=MCC/1.4;use for contactor selection):
RLA(=MCC/1.56;use for breaker & wire size
MCC (Amps):
RPM:
Max Operating Current:
UL File No:
UL File Date:
*Low and High refer to the low and high nominal voltage ranges for which the motor is approved.
105.0 26.6
28-Dec-1984
Performance
19
17.1
*
21.3
Low MFD High MFD Volts User DescriptionPart NoType
014-0006-13 189.0 227.0 330 HIGH TORQUEStart Capacitor
014-0061-20 72.0 86.0 330 LOW TORQUEStart Capacitor
014-0064-14 40.0 0.0 440Run Capacitor
Jasper_RGSubCool
65 /
Jasper_SubC
oolVal
65 /
Jasper_SubC
oolVal
Alternate Applications
Refrigerant Freq (Hz) Phase Voltage Application
R-22 HCFC 50 1
200
R-22 HCFC 60 1
208/230
R-407C HFC 50 1
200 Air Conditioning
Page 1 Of
1
Scott Kohler
05/23/2014
Copyright © 2010 Emerson Climate Technologies, Inc. All rights reserved.