Submittal Sheet
CR38K6E-TF5
HCFC, R-22, 60Hz, 3- Phase, 200/230 V
Air Conditioning
Production Status:
Mechanical
Available for sale to all U.S. customers. Please check with your local Emerson Climate
Technologies Representative for international availability.
Evap(°F)/Cond(°F)
Capacity
(Btu/hr)
Power (Watts):
Current (Amps):
EER (Btu/Wh):
Mass Flow (lbs/hr):
Sound Power (dBA):
Vibration (mils(peak-
Record Date:
45 / 130 45 / 100
37900
3440
49600
2740
10.60 9.10
11.00 18.10
555 640
76 Avg 81 Max
3.6 Avg 4.6 Max
2014-03-06
Number of Cylinders:
2 Displ(in^3/Rev):
Displ(ft^3/hr):Bore Size(in):
Stroke(in):
1.96
0.67
Overall Length (in):
Overall Width (in):
Overall Height (in):
10.23
14.31
9.65
Mounting Length (in):
Mounting Width (in):
Mounting Height (in):
4.05
492.79
7.50
7.50
14.69
Suction Size (in):
Discharge Size (in):
Initial Oil Charge (oz):
Oil Recharge (oz):
Net Weight (lbs):
Internal Free Volume (in^3):
Horse Power:
*Overall compressor height on Copeland Brand Product's specified
mounting grommets.
3/4 Stub
1/2 Stub
43
45
67
Electrical
LRA-High*:
LRA-Half Winding:
LRA Low*:
RLA(=MCC/1.4;use for contactor selection):
RLA(=MCC/1.56;use for breaker & wire size
MCC (Amps):
RPM:
Max Operating Current:
UL File No:
UL File Date:
*Low and High refer to the low and high nominal voltage ranges for which the motor is approved.
85.0 16.7
28-Dec-1984
Performance
11.9
10.7
*
RG(°F)/Liq(°F) 65 / 115 65 / 85
Alternate Applications
Refrigerant Freq (Hz) Phase Voltage Application
R-407C HFC 50 3
200/220 Air Conditioning
R-22 HCFC 50 3
200/220 Air Conditioning
R-407C HFC 60 3
200/230 Air Conditioning
Page 1 Of
1
Scott Kohler
05/23/2014
Copyright © 2010 Emerson Climate Technologies, Inc. All rights reserved.