Submittal Sheet

CR42K6E-TFD
HCFC, R-22, 60Hz, 3- Phase, 460 V
Air Conditioning
Production Status:
Mechanical
Available for sale to all U.S. customers. Please check with your local Emerson Climate
Technologies Representative for international availability.
Evap(°F)/Cond(°F)
Capacity
(Btu/hr)
Power (Watts):
Current (Amps):
EER (Btu/Wh):
Mass Flow (lbs/hr):
Sound Power (dBA):
Vibration (mils(peak-
Record Date:
45 / 130 45 / 100
41700
3810
54500
3010
5.80 5.00
11.00 18.10
610 700
76 Avg 81 Max
4.0 Avg 5.0 Max
2014-03-06
Number of Cylinders:
2 Displ(in^3/Rev):
Displ(ft^3/hr):Bore Size(in):
Stroke(in):
1.96
0.73
Overall Length (in):
Overall Width (in):
Overall Height (in):
10.23
14.56
9.65
Mounting Length (in):
Mounting Width (in):
Mounting Height (in):
4.40
534.59
7.50
7.50
14.94
Suction Size (in):
Discharge Size (in):
Initial Oil Charge (oz):
Oil Recharge (oz):
Net Weight (lbs):
Internal Free Volume (in^3):
Horse Power:
*Overall compressor height on Copeland Brand Product's specified
mounting grommets.
3/4 Stub
1/2 Stub
43
45
69
Electrical
LRA-High*:
LRA-Half Winding:
LRA Low*:
RLA(=MCC/1.4;use for contactor selection):
RLA(=MCC/1.56;use for breaker & wire size
MCC (Amps):
RPM:
Max Operating Current:
UL File No:
UL File Date:
*Low and High refer to the low and high nominal voltage ranges for which the motor is approved.
42.0 8.9
28-Dec-1984
Performance
6.4
5.7
*
7.1
RG(°F)/Liq(°F) 65 / 115 65 / 85
Alternate Applications
Refrigerant Freq (Hz) Phase Voltage Application
R-407C HFC 50 3
380/420 Air Conditioning
R-22 HCFC 50 3
380/420 Air Conditioning
R-407C HFC 60 3
460 Air Conditioning
Page 1 Of
1
Scott Kohler
05/23/2014
Copyright © 2010 Emerson Climate Technologies, Inc. All rights reserved.