6.5.2.7  Monitor the vector rotation through one electrical cycle for proper Hall transitions. 
1 Verify that the red indicator rotates in the same direction as the motor phase angle, 
and that the transition occurs when the needle is between indicators (±30 degrees, 
as shown below). 
2 If the needle and Hall states do not track properly, use the Hall Wiring list box 
(shown below) to swap the amplifier’s Hall wire configuration. 
3 If the red indicator transition leads or lags behind the centered needle by more than 
30 degrees, then try adjusting the Hall Offset in +/- 30 degree increments: 
6.5.2.8  Phasing of a motor with encoder and Halls is complete. Click OK.