5.5.4: Linear Motor Setup Parameters 
View or change the settings described below. Options vary with amplifier model. Metric units are shown 
here. 
S
etting Description 
Manufacturer  Motor maker’s name. Saved in the motor data file. Choose from list or enter 
manually. 
Model Number  Motor model number. Saved in the motor data file. Choose from list or enter 
manually. 
Units  Selects whether the parameters entered in this screen are in Metric or English 
units. 
Mass  The mass of the motor. Used for calculating initial velocity loop tuning values. 
Range: .0001 Kg to 100,000 Kg. Default: .0001 Kg. 
Peak Force  The peak force that the motor can produce. Peak Force divided by Force Constant 
= motor’s peak current limit. Range: 0.00001 to 2,000 N. Default: 0.00001 N. 
Continuous Force  The continuous force that the motor can produce. Used with the force constant to 
calculate continuous current. Range: 0.00001 to 1,000 N. Default: 0.00001 N. 
Velocity Limit  Maximum speed of the motor. Used to calculate the velocity and acceleration 
limits for the velocity loop. Range dependent on encoder resolution. 
Force Constant  Relates the motor's input current to force produced. Sometimes abbreviated as Kf. 
Range: 0.00001 to 2,000 N/Amp. Default: 0.00001 N/Amp. 
Back emf Constant  Relates the motor's input voltage to speed. Sometimes abbreviated as Ke. Used 
for calculating maximum velocity for a given amplifier voltage.
 Range: 0.01 to 
1,000 V/M/Sec. Default: 0.01 V/M/Sec. 
Resistance  Motor resistance line to line. Used for calculating the initial current loop tuning 
values. Range: 0.01 to 327 . Default: 0.01 .
Inductance  Motor inductance line to line. Used for calculating the initial current loop tuning 
values. Range: see Power Output (p. 36).
Magnetic Pole Pair Length  The length of a pair of magnets which equals the distance moved in one electrical 
cycle of the motor. 