D.2: XTL-FA-01 Edge Filter Specifications 
Input 
Voltage, maximum 
373 Vdc 
Current, maximum 
20 Adc 
Output 
Voltage, maximum 
373 Vdc 
Current, maximum 
20 Adc 
Peak Current/Peak Current Time 
40 Adc for 1 second 
Rise/Fall Time 
500 ns (typical) 
Differential Mode Inductance 
82 µH per phase, 162 uH phase-phase (nominal) 
Common Mode Inductance 
220 µH (nominal) 
Nominal Resistance 
27 milliohms per leg, 54 milliohms phase-phase (nominal) 
Agency Approvals 
UL508C, EN60204, RoHS 
Weight 
1 lb. 11 oz. 
D.3: Thermal Considerations 
Cooling Requirements 
When used with XE2/XP2-230-20/800-1782/800-1808, XEL/XML/XPL-230-18 or XEL/XML/XPL-
230-36 drives, the XTL-FA-01 operates below maximum temperature values, and thus requires no 
cooling fan. 
When used with XEL/XML/XPL-40 drives running continuous currents greater than 12 Adc, 
the XTL-FA-01 should be cooled with an external fan. The fan should have a flow rate of at least 
110 CFM. The filter has been tested using the Comair Rotron MD24B2 24 Vdc powered fan. 
Fan Mounting Guidelines 
Most of the filter’s heat is transferred to ambient air, rather than through the heat plate. Thus, it is 
very important to mount the filter and fan in such a way that the fan can blow up through the filter’s 
cover slots. Mount the filter on edge and mount the fan below it so that it blows up through the 
cover slots. 
There is no heatsink option for the XTL-FA-01 edge filter. 