CME 2 User Guide    Control Loops 
Copley Controls  113 
Manually tune the Current Loop 
METHOD: Apply square-wave excitation to the current loop and adjust current loop 
proportional gain (Cp) and current loop integral gain (Ci) to obtain a desired waveform.  
For instance: 
NOTES: 
1) During tuning, observe any warnings that appear to the left of the trace. 
2) Some users prefer the Auto Tune feature. See Current Loop Auto Tune (p. 115). 
1 
 Click the Scope Tool.  
2 
 Choose Current from the Function Generator Apply To: 
list. 
3 
On the Settings tab, make sure Auto Setup is selected. 
Auto Setup automatically sets the following parameters: 
Function Generator Tab 
Parameter 
Description 
Function 
Square Wave. 
Amplitude 
10% of continuous current value. 
Frequency 
100 Hz.  
Settings Tab 
Channel 1 
Commanded current (green). 
Channel 2 
Actual current (white). 
4 
Verify that the Amplitude value is not excessive for the motor. 
Continued… 