User guide
CME 2 User Guide    Homing Methods 
Copley Controls  203 
E.3.6: Hardstop Out to Index 
Direction of Motion: Positive 
Home is the first index pulse on the negative side of the positive hard stop. Initial direction 
of motion is positive. The hard stop is reached when the amplifier outputs the homing 
Current Limit continuously for the amount of time specified in the Delay Time. If a positive 
limit switch is activated before the hard stop, an error is generated. 
H
Index Pulse
Direction of Motion: Negative 
Home is the first index pulse on the positive side of the negative hard stop. Initial direction 
of motion is negative. The hard stop is reached when the amplifier outputs the homing 
Current Limit continuously for the amount of time specified in the Delay Time. If a 
negative limit switch is activated before the hard stop, an error is generated. 
H
Index Pulse
Hardstop Out to Index Methods in Stepper Mode 
In Stepnet amplifiers operating in stepper mode with an encoder, the hard stop is reached 
when the following error is exceeded. When using hardstop methods in stepper mode, do 
not disable following error. 










