User guide
Gain Scheduling   CME 2 User Guide 
222  Copley Controls 
H.1: Configure Gain Scheduling 
Use this procedure to select basic Gain Scheduling options. 
1 
If necessary, Start CME 2 Software (p. 15). 
2 
On the Main screen, choose AmplifierGain Scheduling. 
3 
Choose the Key Parameter: 
Key Parameter 
Description 
Disable Gain Scheduling. 
Disable gain scheduling. 
Use Written Parameter. 
An external controller can write to this parameter using any of several 
protocols and corresponding parameter IDs: Copley ASCII Interface or the 
Copley Indexer 2 Program (ID 0x128), CANopen and EtherCAT(Index 
0x2371), and MACRO I-variable (0x528). 
See the Copley ASCII Interface Programmer’s Guide, the Copley Indexer 2 
Program User Guide, or the Copley CANopen Programmer’s Guide. 
Use Commanded Velocity. 
Schedule gain adjustments based on changes to commanded velocity. 
Use Actual Velocity. 
Schedule gain adjustments based on changes to actual velocity. 
Use Commanded Position. 
Schedule gain adjustments based on changes to commanded position. 
Use Actual Position. 
Schedule gain adjustments based on changes to actual position. 
4 
Optionally set controls: 
Control 
Description 
Use Absolute Value of Key 
Parameter 
If a velocity or position value is chosen for the Key Parameter and this option 
is set, the Key Parameter is interpreted as an absolute value. 
Disable Gain Scheduling 
Until Axis is Referenced 
When this option is set, the scheduled gain adjustments do not take place 
until the axis is referenced (homed). 
5 
Select the gains that you wish to adjust by schedule. The choices are Pp, Vp, Vi and 
Current Offset (A). For each gain you select, a column will be enabled in the Gain 
Scheduling Table. 
6 
Continue with Set Up the Gain Scheduling Table(s) (p. 223). 